7.1 - EASY SETTINGS OF THE STROKE
With the simple learning the control unit autonomously performs all the procedure and calculation of slowdowns, which will be set
with the same percentage both in opening and closing (base parameter LSI).
Before starting the procedure make sure you have installed the electric limit switches and have them properly
adjusted.
Make a check of the settings and eventually customize them.
Unlock the automation and move it to the middle of the stroke.
1.
Press at the same time the "UP" and "MENU" buttons for at least 5
seconds until the display shows LOP.
If the automation DOESN'T MOVE in opening, press the "DOWN" button
2.
to stop the learning. The display shows L--.
Press the "SS" button to restart the procedure: the automation moves in
3.
opening, at reduced speed, until it reaches the limit switch. In this phase
the display shows LOP.
Reached the opening limit switch, the automation moves automatically
4.
in closing, at running speed, until it reaches the closing limit switch. In
this phase the display shows LCL.
Reached the closing limit switch, the automation moves automatically in
5.
closing, at running speed, until it reaches the opening limit switch. In
this phase the display shows LOP.
Reached the opening limit switch, the automation moves in closing at
6.
running speed and with the slowdowns set into the menu LSI.
WARNING! in the event of a safety device intervention, the learning is stopped and will appear on the display L--.
Press the "SS" button to start again the learning from the 3rd point.
10 / 28
UP
MENU
UP
MENU
SS
UP
ENG
firmware BIOS124P01
DOWN
SS
DOWN
DOWN
MENU
SS