Specification of TX-TOS1413
Function
Analogue Input (0 - 10V) Capacity
Demand
Mode Input (Cool / Heat)
Digital Output (DO_1, DO_2)
Terminal A1 / A2: Analogue Input Capacity Demand
• Be sure not input more than DC10V in analogue input terminal.
• To ease the integration of the DX COIL with the DDC the capacity
control is able to operate with a STEPPED or LINEAR function from the
analogue input.
• To select either a STEPPED (default) or LINEAR response, from the
analogue input, use SW03 bit2 located on TX-TOS1413.
• Capacity demand is changed by setting temperature of DDC and
discharge air temperature.
SW3 bit-2
OFF
ON
▼ When connected to SMMS-e, 7
A/I_1: Demand 0~10V Stepped Control (SW3 bit2 OFF: Default)
Cooling Mode
STEPPED Capacity Demand
10.00
100%
8.00
7.25
95%
6.50
90%
5.75
85%
5.00
80%
4.25
75%
3.50
70%
2.75
65%
2.00
60%
1.25
55%
0.50
50%
No Operation
0%
0.00
A/I_1: 1 Demand 0~10 V Linear Control (SW3 bit2 ON)
Cooling Mode
LINEAR Capacity Demand
10.00
9.50
100%
9.00
95%
8.50
90%
8.00
85%
7.50
80%
7.00
75%
6.50
70%
6.00
65%
5.50
60%
5.00
55%
4.50
50%
No Operation
0%
0.00
23-EN
Terminal
C23 / C24
D31/ D32 & D33 / D34
Function
STEP response to analogue input
LINEAR response to analogue input
Heating Mode
STEPPED Capacity Demand
10.00
(V)
100%
9.50
95%
8.75
8.00
90%
7.75
7.25
85%
7.00
6.50
80%
6.25
75%
5.75
5.50
5.00
70%
4.75
4.25
65%
4.00
3.50
60%
3.25
2.75
55%
2.50
50%
2.00
1.75
45%
1.25
1.00
0.50
40%
0.25
No Operation
0%
0.00
0.00
Heating Mode
LINEAR Capacity Demand
10.00
(V)
9.50
100%
9.30
9.00
95%
8.80
8.50
90%
8.30
8.00
85%
7.80
7.50
80%
7.30
7.00
75%
6.80
6.50
70%
6.00
6.30
65%
5.80
5.50
60%
5.30
5.00
55%
4.50
4.80
50%
4.30
4.00
45%
3.50
40%
No Operation
0%
0.00
0.00
Max. Cable Length (m)
A1 / A2
▼ When connected to SMMS-u
A/I_1: Demand 0~10V Stepped Control (SW3 bit2 OFF: Default)
Cooling Mode
STEPPED Capacity Demand
10.00
(V)
9.25
8.50
8.00
7.75
7.25
7.00
6.50
6.25
5.75
5.50
5.00
4.75
4.25
4.00
3.50
3.25
2.75
2.50
2.00
1.75
1.25
1.00
0.50
0.25
No Operation
0.00
0.00
A/I_1: Demand 0~10V Linear Control (SW3 bit2 ON)
Cooling Mode
LINEAR Capacity Demand
10.00
(V)
9.50
9.30
9.00
8.80
8.50
8.30
8.00
7.80
7.50
7.30
7.00
6.80
6.50
6.30
6.00
5.80
5.50
5.30
5.00
4.80
4.50
4.30
3.80
3.30
No Operation
0.00
0.00
– 23 –
Cable Specification
200
Shield wire: 0.5~1.0 mm²
100
Non shield wire: 0.5~1.0 mm²
500
Non shield wire: 0.5~1.0 mm²
0-10V
A1
+
A/I_1
Heating Mode
STEPPED Capacity Demand
10.00
(V)
9.50
8.75
100%
8.00
7.75
95%
7.25
7.00
90%
6.50
6.25
85%
5.75
5.50
80%
5.00
4.75
4.25
70%
4.00
3.50
60%
3.25
50%
2.75
2.50
40%
2.00
1.75
30%
1.25
1.00
0.50
20%
0.25
0%
0.00
0.00
LINEAR Capacity Demand
10.00
(V)
9.50
100%
9.30
9.00
95%
8.80
8.50
90%
8.30
8.00
85%
7.80
7.50
80%
7.30
7.00
70%
6.80
6.50
60%
6.00
6.30
50%
5.80
5.50
40%
5.30
5.00
30%
4.50
4.80
20%
4.30
4.00
3.50
0%
0.00
0.00
A2
-
(V)
100%
9.25
90%
8.50
80%
7.75
70%
7.00
60%
6.25
50%
5.50
45%
4.75
40%
4.00
35%
3.25
30%
2.50
25%
1.75
20%
1.00
15%
0.25
No Operation
0%
0.00
Heating Mode
(V)
100%
9.30
90%
8.80
80%
8.30
70%
7.80
60%
7.30
50%
6.80
45%
6.30
40%
5.80
35%
5.30
30%
4.80
25%
4.30
20%
3.80
15%
3.30
No Operation
0%
0.00