Procedure
Push "TEST" + "SET" + "CL" buttons simultaneously for at
least 4 seconds.
After a while, the display flashes as shown in the figure.
Confirm that the CODE No. is [ 10 ].
• If the CODE No. is not [10] push "TEST" button to erase
the display content and repeat the procedure from the
beginning.
(No operation of the
remote controller is
accepted for a while
after "TEST" button is
pushed).
(* Display content varies with the
indoor unit model.)
3
Procedure
Each time you push "UNIT" button, indoor unit numbers in
the control group change cyclically.
4
Procedure
Using "TEMP" buttons, specify CODE NO. [ 11 ].
5
Procedure
Using timer "TIME" buttons, select SET DATA [ 00
Dx-coil controller
Dx-valve kit
Capacity Code
(DN11)
].
8HP
10HP
16HP
RBM-A101VAE
0021
0023
0026
6
Procedure
Push "SET" button.
When the display changes from flashing to lit, the setup is
completed.
• To change settings of another indoor unit, repeat from
3
procedure
.
• To change other settings of the selected indoor unit,
repeat from procedure
settings. To make settings after "SET" button was
pushed, repeat from procedure
7
Procedure
When settings have been completed, push "TEST" button
to determine the settings.
When "TEST" button is pushed, [SETTING] flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While [SETTING] is flashing, no operation of the remote
controller is accepted).
SET DATA
18HP
20HP
32HP
TCB-IFDDC201E
RBM-A201VAE
0027
0028
0035
– 26 –
4
. Use "CL" button to clear the
3
.
36HP
40HP
0037
0039
EN
26-EN

Publicidad

loading

Este manual también es adecuado para:

Rbm-a101vaeRbm-a201vae