DANGER
Danger of electric voltage!
Products with extraction power control (frequency inverters) are
intended for protection by line protection fuses.
If the product is operated on a mains supply with a residual current
circuit breaker (RCCB) connected upstream, the following must be
observed.
Since the operation of the frequency inverter on the protective earth
conductor can cause a direct current, the residual current circuit breaker
(RCCB) connected in series with the mains must meet the following
requirements.
Category
Rated current
type:
Type B
40 A
Type B
63 A
Type B
80 A
Type B
100 A
Type B
125 A
Tab. 13: Requirements for residual current circuit breaker
CAUTION
Health hazard due to noise!
The product can produce noise, please refer to information in the
technical data. In connection with other machines and/or local
conditions, a higher noise level can occur at the operation site of the
product. In this case, the operating company is obliged to provide the
operating personnel with the appropriate protective equipment.
1502778-02
Tripping fault current Note
300 mA
300 mA
300 mA
300 mA
300 mA
- 61 -
short time-delayed
short time-delayed
short time-delayed
short time-delayed
short time-delayed
EN