AIR PURGING
Air containing moisture remaining in the refrigeration cyde may cause a malfunction on the compressor.
After connecting the indoor and outdoor units, evacuate air and moisture from refrigerant cyde using a
vacuum pump, as shown below.
Note: Because the system pressure is high and also to protect the environment, be sure not to discharge
the refrigerant to the air directly.
Service port
C_)
C_)
(2) Turn
( 8 ) Tig
How to Purge Air Tubes:
I . Unscrew and remove caps from 2 and 3-way valves.
2. Unscrew and remove cap from service valve.
3. Connect vacuum pump flexible hose to the service valve.
4. Start vacuum pump for I 0-15 minutes until it reaches an absolute vacuum of I O mm Hg.
5. With vacuum pump stili running dose the low pressure knob on vacuum pump manifold. Then stop
vacuum pump.
6. Open 2-way valve I /4 turn, then dose it after I O seconds. Check tightness of all joints using liquid soap
or an electronic leak detector.
7. Turn 2 and 3-way valves stem. Disconnect vacuum pump flexible hose.
8. Replace and tighten all valve caps.