FSW OP = Opening safety devices contact (N.C.)
Safety devices are all devices (photocells, sensitive edges,...) with N.C. contact, which, if there is an obstacle in
the area they protect, operate to stop or reverse door opening movement.
They have no effect during closing.
If the opening safety devices are engaged with the door closed, they inhibit any Open pulse.
To install several safety devices, connect the N.C. contacts in series.
Note: If opening safety devices are not connected, jumper connect inputs "FSW OP" and "-FSW TX".
8
FSW CL = Closing safety devices contact (N.C.)
Safety devices are all devices (photocells, sensitive edges,...) with N.C. contact, which, if there is an obstacle in
the area they protect, operate to reverse door closing movement.
They have no effect at opening.
If the closing safety devices are engaged with the door open, they inhibit any Open pulse.
To install several safety devices, connect the N.C. contacts in series.
Note: If closing safety devices are not connected, jumper connect inputs "FSW CL" and "-FSW TX".
9
STOP = STOP Command (N.C.)
This is any device (e.g. a push-button) which, by opening a contact, stops door movement.
To install several stop devices, connect the N.C. contacts in series.
Note: If Stop devices are not connected, jumper connect "STOP" to the inputs Common.
10
OPEN = OPEN Command (N.O.)
This is any device (a push-button, a detector,...) which, by closing a contact, supplies an opening (or closing)
pulse to the door.
To install several Open devices, connect N.O. contacts in parallel.
4.4
CONNECTOR J4 (low voltage)
Connector J4 is used for rapid connection of MINIDEC, DECODER cards and 5-Pin RP RECEIVERS.
Install by fitting the auxiliary cards so that their components side faces the inside of the control board.
Insert and remove the cards after cutting power.
5.
SIGNALLING LEDs
An LD1 led on the control board signals the correct power suppy to the control board.
L
= powered control unit
ED LIGHTED
6.
PROGRAMMING
To program operation of the automated system, you have to set the microswitches DS1 on the control board.
Descriptions and tables for different settings and type of function (fig. 4 and 5) are shown below.
6.1
OPERATING TIME
Use microswitches SW1 and SW2 to set an operating time enabling the electric motor to receive power for a few
seconds after the door reaches the mechanical stops. This setting is also the maximum time for reaching the electric
opening and closing limit-switches (optional), if used.
6.2
OPERATING LOGIC AND PAUSE TIMES
You can adjust the pause time through the microswitches SW3,
SW4 and SW5 if you use the Automatic logic.
6.3
ELECTRONIC CLUTCH
The control board is supplied with an electronic system for
adjusting motor torque, which (according to adjustment)limits
door thrust in the event of any obstacles. After the obstacle is
removed, the door resumes moving either until it reaches the
limit-switch or when operating time has elapsed. We recommend
setting the electronic clutch with microswitches SW6,SW7 and
SW8 in compliance with current standards.
L
= unpowered control unit
ED OFF
7
SW1 SW2
Operating time
on
on
30 sec.
off
on
25 sec.
on
off
20 sec.
off
off
17 sec.
Fig. 4
1 2 3 4 5 6 7 8 9 101112
ON
OFF
SW3 SW4 SW5
Logic
on
on
on
semi-automatic
off
on
on
automatic
on
off
on
automatic
off
off
on
automatic
on
on
off
automatic
off
on
off
automatic
on
off
off
automatic
off
off
off
automatic
ENGLISH
SW6 SW7 SW8 Force
on
on
on
min
off
on
on
on
off
on
off
off
on
on
on
off
off
on
off
on
off
off
off
off
off
max
Pause time
5 sec.
10 sec.
15 sec.
20 sec.
30 sec.
45 sec.
60 sec.