Descargar Imprimir esta página

Lamborghini Caloreclima ALHENA TECH H Serie Instrucciones De Uso, Instalación Y Mantenimiento página 332

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

•setting parameter P67 to 1
•after changing the value of parameter P68
•after setting parameter b27 to 5 for replacement of components such as the electrode, burner,
gas valve, fan or for installations with maximum flue resistance
•in case of fault conditions A01, A06 or other faults when required (see table 11. Respect the
sequence of fault cures).
The calibration procedure [Auto Setup] resets the combustion parameters previously recorded
and must be done only in the cases described above.
Test mode [Test]
Do a heating or DHW request (with optional hot water tank connected).
1.Access the Main menu [MENU] with the
button
.
Follow the path installer menu [Service]
>enter the Password 1234 (see fig. 17)
>test mode menu [Test].
Confirm with the button
2.After ignition, the power goes to Medium
"med". When the combustion value is
stable, "med ok" is displayed (point
3.The heating buttons are used to vary the 4
power levels: min (Minimum power), med
(Medium power), max CH (CH Maximum
power) and max (DHW maximum power)
(point
).
a
4.Only when the step value at the set power
is followed by "ok" (med ok, min ok...) can
the CO
be adjusted with the DHW but-
2
tons. Pressing the
crease the "Offset" value by one unit
(point
). By pressing the
b
DHW buttons for more than 2 sec., the
Offset value will change by 3 units (Offset
adjustment is possible only in steps:
max, med and min).
When the Power value is followed by "ok"
the combustion value will be saved.
To exit the test mode [Test] hold down the button
If the Test mode [Test] is active and enough hot water is drawn to activate the DHW mode, the
boiler remains in Test mode [Test] but the 3-way valve switches to DHW.
The Test mode [Test] is automatically disabled in any case after 15 minutes.
Installer menu [SERVICE]
ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARA-
METERS.
Access the Main menu [MENU] with the button
Follow the path installer menu [Service] >enter the Password 1234 (see fig. 17). Confirm with
the button
.
332
.
).
a
DHW button will in-
and
cod. 3541V622 - Rev 00 - 05/2022
ALHENA TECH H
5.The "Offset" adjustment range is from -8 to
+8. Increasing the value decreases the
CO
, decreasing it increases the CO
2
CO
adjustment must not be done with
2
less than 500 burner operation hours
because the system adjusts itself.
TEST
Step:
med ok
Offset:
Power:
53%
CH temp:
Alarm:
none
fig. 40
.
.
.
2
a
b
0
43°
EN

Publicidad

loading