Connect the external control cables to the control unit
See
Connecting the external control cables to the control unit (page 289)
Step
Tasks
1
Connect the intermediate control cables between the control unit and the drive module as
follows:
• Remove the plate which covers the slot in the middle front cover of the drive module at
the front or left side.
• Install a rubber grommet (item 6 in the accessories box) to the slot.
• Route the cables through the slot.
• Connect the power supply cable to terminal X2.
• Connect the STO cable to the INU STO connector.
• Connect the fiber optic cables to the QOIA V8, V13, V2 and V7 connectors.
I S U p a n e l
C a t 5 c a b l e
Note: ISU ext. 24VDC connector is for supplying external 24 V DC to the line-side converter
control unit if needed. ISU panel connector is for connecting the control panel to the line-
side converter control unit if needed.
2
Disconnect the control panel cable from connector X13 on the control unit.
3
Loosen the mounting screws of the control panel holder and take the holder off.
4
Install the control cable grounding clamp plate to the control unit.
EN – Quick installation and start-up guide 15