272 Technical data and references
Technical data
■
•
Minimum voltage at IN1 and IN2 to be interpreted as "1": 17 V DC
•
STO reaction time (shortest detectable break): 1 ms
•
STO response time: 2 ms (typical), 30 ms (maximum)
•
Fault detection time: Channels in different states for longer than 200 ms
•
Fault reaction time: Fault detection time + 10 ms
•
STO fault indication (parameter 31.22 ) delay: < 500 ms
•
STO warning indication (parameter 31.22 ) delay: < 1000 ms
•
Safety integrity level (SIL, EN 62061): 3
•
Performance level (PL, EN ISO 13849-1): e
The drive STO is a type B safety component as defined in IEC 61508-2.
For the full safety data, exact failure rates and failure modes of the STO function, refer
to the drive hardware manual.