To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the "Easy I.DN setting" procedure
1
2
3
4
5
(
→
→
→
→
).
• Select "3. Heating temp. shift" from the "Easy I.DN
setting" menu.
• Select the Set data for "Heating temp. shift" from
following table.
Set data
Detection temp shift value
+0K
No shift
+1K
1.8°F (+1°C)
3.6°F (+2°C)
+2K
(Factory default)
+3K
5.4°F (+3°C)
+4K
7.2°F (+4°C)
+5K
9.0°F (+5°C)
+6K
10.8°F (+6°C)
29-EN
Selecting swing type and
louver lock
Refer to the owner's manual for how to select swing
type and louver lock.
• About "Dual swing"
"Dual" means that louvers 01 and 03 are directed
and swing in one direction and louvers 02 and 04 are
directed and swing in the opposite direction.
(When louvers 01 and 03 are directed downward,
louvers 02 and 04 are directed horizontally.)
• About "Cycle swing"
The four louvers swing independently at respective
timings.
03
04
02
01
Drain pipe
Refrigerant pipe
– 15 –
TA sensor selection
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote control sensor to
sense the temperature around the remote control.
Select items following the "Easy I.DN setting"
procedure
1
2
3
4
5
(
→
→
→
→
).
• Select "4. TA sensor selection" from the "Easy I.DN
setting" menu.
• Select the Set data for "TA sensor selection" from
following table.
Set data
TA sensor selection
Body
Sensor of the indoor unit (Factory default)
RC
Sensor of the remote control
• When "RC" is selected,
lights up. However, it is
not displayed when it is set as a sub-remote control.
• When
flashes, the remote control sensor is
defective. Select the Set data "Body" or replace the
remote control.
Group control
In a group control, a remote control can control up to
maximum 8 or 16 units. (Depending on the outdoor
unit.)
• The wired remote control only can control a group
control. The wireless remote control is unavailable
for this control.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to "7.
Electrical connection" in this Manual.
• Wiring between indoor units in a group is performed
in the following procedure.
• Connect the indoor units by connecting the remote
control wires from the remote control terminal blocks
(A, B) of the indoor unit connected with a remote
control to the remote control terminal blocks (A, B) of
the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
30-EN