Fixing the installation plate
You can select the direction of the drain hose depending on where you want to install the indoor unit. Therefore before fixing
the installation plate to a wall or a window frame, you must determine the position of the 65 mm hole through which the cable,
pipe and hose pass to connect the indoor unit to the outdoor unit.
When facing the wall, the pipe and cable can be connected from the:
• Right (A)
• Left (B)
• Underside_right (C)
• Rear_right or left (D)
1. Determine the position of the pipe and drain hose hole as seen in the picture and drill the hole with an inner diameter
of 65 mm so that it slants slightly downwards.
150mm or more to ceiling
100
120mm or more
to wall
Rear side refrigerant
pipe hole Φ65
150mm or more to ceiling
293
120mm or more
to wall
Rear side refrigerant
pipe hole Φ65
2. Fix the indoor unit.
If you fix the indoor unit on a wall
(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.
• I f you mount the plate to a concrete wall using plastic anchors, make sure that gaps
between the wall and the plate, created by projected anchor, is less than 20 mm.
If you fix the indoor unit on a window frame
(1) Determine the positions of the wooden uprights to be attached to the window frame.
(2) Attach the wooden uprights to the window frame giving attention to the weight of the indoor unit.
(3) Attach the installation plate to the wooden upright using tapping screws.
If you fix the indoor unit on a gypsum board
(1) Use stud finder to find out locations of the studs.
(2) Fix the plate hanger on two studs.
• S earch for other spots if there are less than two studs, or the distance between the studs are different from the
plate hanger.
• Fix the installation plate without inclining to one side.
• M ake sure that a wall can withstand the weight of the product. If you install the product in a place where it is not
strong enough to withstand the product weight, the unit could fall and cause injury.
Midea ODM Latin America IB&IM_HP_EN.indd 34
Direction of pipe
A
D
D
C
Indoor unit outline
A
95
120mm
or more
to wall
Rear side refrigerant
800
Indoor unit outline
C
163
120mm
or more
to wall
21.5
1045
English-34
B
150mm or more to ceiling
110
120mm
or more
to wall
pipe hole Φ65
model
09/12
18
24
• M ake sure to drill only one hole after
choosing the direction of the pipe.
Indoor unit outline
B
100
120mm
or more
to wall
940
Plate Type
A
B
C
Plastic
Anchor
Wall
<20 mm