Transfer
Adjustment
Menu item
range
Transfer start diff. 6 ... 10 ... 20 K
Transfer stop diff. 3 ... 5 ... 17 K
Table 17
Solar DHW
WARNING: Risk of scalding!
▶ If DHW temperatures above 60 °C are set or
thermal disinfection is switched on, a mixing
valve must be installed.
Adjustment
Menu item
range
DHW controller
Boiler
act.
external
module 1
external
module 2
Therm.dis./daily
Yes
ht cyl1
No
Therm.dis./daily
Yes
ht cyl3
No
Table 18
MS 100
Function description
If the differential set here between cylinder 1 and cylinder 3 is exceeded and all
conditions for switching on have been met, the transfer pump is on.
If the differential between cylinder 1 and cylinder 3 falls below the value set here, the
transfer pump is off.
Function description
One DHW system is installed and is controlled by the heat appliance.
2 DHW systems are installed. One DHW system is controlled by the heat appliance.
The second DHW system is controlled by an MM 100 module (coding card set to 10 -
accessory).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW
system that is controlled by the heat appliance.
One DHW system is installed and is controlled by an MM 100 module (coding card set
to 9).
2 DHW systems are installed. Each DHW system is controlled by an MM 100 module
(coding card set to 9/10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW
system that is controlled by external module 1 (coding card set to 9).
2 DHW systems are installed. One DHW system is controlled by the heat appliance.
The second DHW system is controlled by an MM 100 module (coding card set to 10).
2 DHW systems are installed. Each DHW system is controlled by an MM 100 module
(coding card set to 9/10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW
system that is controlled by external module 2 (coding card set to 10).
Switches thermal disinfection and daily heat-up of cylinder 1 on or off.
Switches thermal disinfection and daily heat-up of cylinder 3 on or off.
Commissioning | 39
6 720 815 256 (2014/10)