WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by
the power supply. Do NOT touch them with bare hands.
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10  minutes,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing. The
voltage MUST be less than 50 V DC before you can touch
electrical components. For the location of the terminals,
see the wiring diagram.
b
l
a
DC
DC
AC
-
+
k
j
a
DB1 diode bridge
b
S90 thermistor lead wire
c
LED A
d
S40 thermal overload relay lead wire
e
S20 (white) room A electronic expansion valve coil
f
S21 (red) room B electronic expansion valve coil
g
S80 (white) 4-way valve lead wire connector
h
S70 fan motor lead wire
i
S99 heating lock
j
S91 (red) liquid thermistor lead wire
k
S92 (white)gas thermistor lead wire
l
Multimeter (DC voltage range)
7.1
Specifications of standard wiring
components
Component
Power supply
Voltage
cable
Phase
Frequency
Wire type
Interconnection cable
(indoor↔outdoor)
Recommended circuit breaker
2MXM40+50A
R32 Split series
3P600450-5L – 2021.12
c
d
i
h
g
f
e
220~240 V
1~
50 Hz
3-core cable 2.5 mm
H05RN-F (60245 IEC 57)
H07RN-F (60245 IEC 66)
3-core cable 4.0 mm
H07RN-F (60245 IEC 66)
2
4-core cable 1.5 mm
2
2.5 mm
and applicable for
220~240 V
H05RN-F (60245 IEC 57)
16 A
Component
Residual current device
7.2
To connect the electrical wiring to
the outdoor unit
1 Remove the switch box cover (2 screws).
2 Connect the wires between the indoor and outdoor units so that
the terminal numbers match. Make sure to match the symbols
for piping and wiring.
3 Make sure to connect correct wiring to correct room (A to A, B
to B).
a-A
1
e-A
a
Terminal for room (A, B)
b
Circuit breaker
c
Residual current device
d
Power supply wire
e
Interconnection wire for room (A, B)
f
Wire retainer
4 Tighten the terminal screws securely using a Phillips
screwdriver.
5 Check that the wires do not disconnect by pulling them lightly.
6 Firmly secure the wire retainer to avoid external stress on wire
terminations.
7 Pass the wiring through the cutout on the bottom of the
protection plate.
8 Make sure the electrical wiring does not contact with the gas
piping.
1
2
3
2
2
or
A
1 2 3 1 2 3
7 Electrical installation
MUST comply with
applicable legislation
a-B
2
3
1
2
3
L
N
f
b
c
d
e-B
1
2
3
L
N
B
Installation manual
13