Fully automatic mode
The light automatically switches ON and OFF in response
to light level and human presence / movement. Light can
be switched ON and OFF manually at any time. This tem-
porarily interrupts the automatic switching function.
Presentation mode
If light is switched OFF via a push-button, the sensor acti-
vates the presentation mode. The load remains switched
OFF until movement is detected. As soon as movement
is no longer being detected and the stay-ON time has
elapsed, the sensor returns to normal sensor mode.
Button input
The pushbutton switch connected provides the ON / OFF
function and can switch lighting ON and OFF.
A pushbutton is required for operating the sensor in semi-
automatic mode.
Manual override can be activated via a connected push-
button switch. Pressing the pushbutton switch 2 x activa-
tes light ON for 4 hours. Pressing the pushbutton switch
once again before the 4 hours ON period has elapsed
returns the sensor to normal fully or semi-automatic mode.
For PD only: switches OFF in relation to ambient
brightness
If light level falls below the selected twilight threshold, ligh-
ting is switched OFF even if movement or human presence
is being detected.
Intelligent parallel connection of several sensors
L' detection provides the option of connecting as many
as 10 sensors in parallel. When a sensor is triggered, light
switches ON and all sensors in the network assume day-
light mode. This has the advantage of being able to detect
movements irrespectively of ambient brightness and letting
stay-ON time expire.