OPTIONAL FUNCTION
No.
Item
Optional function
Circulation function at
2
b2
heating thermo OFF
3
Not Used
b3
Change of filter cleaning
4
b4
period
5
Locking of operation mode
b5
Locking of setting
6
b6
temperature
Setting operation mode as
7
b7
cooling only
Automatic COOL/HEAT
8
b8
operation
9
Locking of fan speed setting
bg
10
Not available
bA
Cooling setting temperature
11
bb
correction
12
Not used
bC
13
Not used
bd
14
Not used
bE
15
Not used
C1
16
Not available
C2
17
Not used
C3
10
PMML0497 rev.1 - 12/2020
Individual
Settings
Setting
Function disabled
00
(factory setting)
01
Function enabled
00
-
-
01
00
Standard (1200 hours)
01
100 hours
1200 hours
02
(factory setting)
03
2500 hours
04
No indication
Function disabled
00
(factory setting)
×
01
Function enabled
Function disabled
00
(factory setting)
×
01
Function enabled
Function disabled
00
(factory setting)
×
01
Function enabled
00
Function disabled (factory setting)
×
01
Function enabled
Function disabled
00
(factory setting)
×
01
Function enabled
"- -"
-
Not available
permanent
00
No compensation (factory setting)
Setting temperature decreased by
01
×
1 ºC
Setting temperature decreased by
02
2 ºC
00
-
-
01
00
-
-
01
00
-
-
01
00
-
-
01
"- -"
-
-
permanent
00
-
-
01
Setting conditions
This function keeps the fan running
during the thermo OFF sequence,
at the fan speed set on the remote
control switch, to prevent the
stratification of air in the room.
Use as 00 conditions
This function is used to modify the
period of operation after which
the air filter cleaning indication is
shown in the remote control.
For RPk-FSN(H)3M models, the
factory setting is b4=00: Standard
setting 200 hours.
This function prevents the
modification of the operation
mode of the unit from the remote
controller and from central
controls, once it has been
selected.
This function prevents the
modification of the setting
temperature of the unit from
the remote controller and from
central controls, once it has been
selected.
This function is used to limit the
operation mode to cooling only
and to prevent heating mode from
being enabled.
This function enables the selection
of Auto cool/heat operation mode.
If the function is not activated, Auto
cool/heat mode cannot be selected
on the remote control switch.
This function prevents the
modification of the fan speed of
the unit from the remote controller
and from central controls, once it
has been selected.
This function decreases the
setting temperature and is used to
produce longer cooling periods.
Use at 00 conditions
Use at 00 conditions