Descargar Imprimir esta página

Hitachi PC-ARH1E Manual De Instalación Y Funcionamiento página 20

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 35
OPTIONAL FUNCTION
No.
Item
Optional function
Control by the temperature
sensor of the remote control
switch
?
N O T E
The remote control switch
shall be installed in a proper
place for the correct detection
of room temperature by its
temperature sensor.
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB
?
N O T E
The remote sensor shall be
installed in a proper place for
the correct detection of room
temperature.
22
C8
Model
RPF(I)-FSN2E
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB
?
N O T E
The remote sensor shall be
installed in a proper place for
the correct detection of room
temperature.
Models
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
RPIM-FSN4E(-DU)
RPk-FSN(H)3M
23
Not available
Cg
24
Not available
CA
Selection of forced stoppage
25
Cb
logic
26
Not used
CC
12
PMML0497 rev.1 - 12/2020
Individual
Settings
Setting
Control by the air inlet sensor of
00
indoor units (factory setting)
Control by the temperature sensor
01
of the remote control switch
Control by the average value of
the air inlet sensor of indoor units
and the temperature sensor of the
02
remote control switch.
(Air inlet + Remote control switch)/2
When a remote sensor is connected
to THM4, this remote sensor is
00, 01, 02
used as control sensor, whichever
the setting for C8
(factory setting C8=00)
Air temperature control using
the average value of the air inlet
thermistor and the remote sensor
00, 02
(factory setting C8=00)
(Air inlet + Remote sensor)/2
Air temperature control using the
01
remote sensor
"- -"
-
permanent
"- -"
-
permanent
Forced stoppage input: A contact,
00
normally open contact (factory
setting)
Forced stoppage input: B contact,
01
normally closed contact
00
-
-
01
Setting conditions
This function specifies the
temperature sensor to be used as
control sensor by the indoor unit.
This function determines the logic
operation for the forced stoppage
contacts.
Use at 00 conditions
Description

Publicidad

loading