Descargar Imprimir esta página

Riello 40 G10 Instrucciones Para La Instalación, Uso Y Mantenimiento página 27

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 35
TECHNICAL DATA
TYPE
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
For use on hot air generator the burner must be fitted with control box type 479SE or 539SE.
Burner with CE marking in conformity with EEC Directives: Electromagnetic Compatibility 2014/30/UE,
Low Voltage 2014/35/UE, Machines 2006/42/EC.
The burner meets protection level of IP 40, EN 60529.
8
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air damper
7 – Hydraulic jack with air damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Combustion head adjustment screw
2351
464T1
54 – 120 kW
Light oil, max. viscosity at 20 °C: 6 mm
Single phase, 230 V ± 10%
Run current 0.8 A – 2850 rpm – 298 rad/s
4 F
Secondary 8 kV – 16 mA
Pressure 7 – 15 bar
0.170 kW
Fig. 1
7
6
6
9
D8067
HYDRAULIC JACK OPERATION 7)(Fig. 1)
DANGER
1
GB
4.5 – 10 kg/h
2
/s
~
50Hz
2
It is strongly recommended a periodic check of
the pump pressure operation (annually or bet-
ter every six months, if the burner operation is
continuous).
If the value is lower than 1 bar, compared to
that one of the initial setting, please check the
cleaning of the pump and line filters.
In case the pressure setting was not restora-
ble, please replace the pump, in order to guar-
antee that the pump pressure during the pre-
purge time is at least 3.7 bar.
ENGLISH
10
1
5

Publicidad

loading

Este manual también es adecuado para:

3746412