Verification
Sets the verification sequence for the alarms.
Sequential verification on
If sequential verification is set to On and
•
If there is more than one sensor (door contacts or PIR) with attribute set to Burglar:
•
If the first sensor is triggered, the control panel will send an SMS with burglar.
o
If the second sensor is triggered within 30 minutes, the control panel will send an SMS with Alarm
o
confirm.
Sequential verification off
•
If sequential verification is set to Off, the control panel will only send an SMS with Burglar.
Final Door
•
If the Final Door option is set to on and
•
If the alarm system is set to away arming and
a door contact is set as Entry device
•
The system will automatically full arm once the door contact is detected as closed, even if the countdown period
is not yet finished.
Interference
Allows setting whether the control panel should detect signal jamming or not.
When Detection is set to On, whenever the signal jamming period lasted longer than 30 seconds, this error
•
will be logged, reported to the Central Monitoring Station and displayed on the LCD to warn the user.
When the Detection Off is selected, control panel will not check interference status.
•
RC Ent E (= remote controller entry enabled)
This feature is used to prevent the alarm from being turned off with a remote control without unlocking a door
first, for example if the remote has been stolen.
To access the function
•
you need to first activate and entry point device to be able to disarm the alarm system.
If the remote controller entry is set to On:
•
a remote control can disarm the alarm system without unlocking a door first.
Mobility
This option disables or enables the Mobility Timer and sets a countdown period. Options available are Disable, 4
hours, 8 hours and 12 hours.
If the Mobility Timer is enabled, it will count down the pre-programmed time length. When the timer times out
without being reset, a report will be made to the Programmed phone numbers.
V. 04 – 11/02/2016
:
CTC1000
16