5.2.2.2 "AUTO" MODE
GO
At the end of the test, in case the
resistance
value
results to be lower than R
(depending on the selected voltage
see following Table 3), the test is
effected at the selected rated
voltage value and a stable value of
the resistance is detected, the
instrument emits a double sound
signal
indicating
outcome of the test displays one
screen
similar
alongside.
SAVE
Press the GO key. The instrument effects the measurement ending
when the measured value gets stable.
Note: Press the GO key again if the test is to be stopped
MΩ
detected
MAX
the
positive
to
the
screen
Rated voltage value selected for the test.
The test can be stored pressing the SAVE key twice (according to
paragraph 0).
R
ISO
1.18
MΩ
500 V
18
AUTO
17
Insulation
resistance
value R
ISO.
s
Test duration.
In this case the
measurement
got stable after
18 seconds.
Automatic mode.