Descargar Imprimir esta página

Vestfrost VT146 Instrucciones Para El Uso página 4

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 42
GB
Installation and start-up
Placement
For safety and operational reasons, the
appliance must not be installed outdoors.
The appliance should be placed on a
stable, level surface in a dry, well-ventilated
room (max. 75% relative air humidity).
Never place the appliance close to sources
of heat such as cookers or radiators, and
avoid placing it in direct sunlight. Standard
EN378 specifies that the room in which you
install your appliance must have a volume
of 1m³ per 8 g of hydrocarbon refrigerant
used in the appliances , so as to avoid the
formation of inflammeable gas/air mixtures
in the room where the appliance is located
in the event of a leak in the refrigerant
circuit. The quantity of the refrigerant used
in your appliances is indicated on the
nameplate.
Room temperature
The appliance is designed to operate at
limited ambient temperatures according to
the appliance climatic category specified
on the nameplate. Data regarding climate
Class and other technical information are
given on the nameplate on the rear of the
appliance.
Climate class
SN
N
ST
T
Ventilation
It is important that the appliance be well
ventilated and that air can circulate unhin-
dered above, below and around it. Figure 2
illustrates how the necessary air circulation
can be ensured.
Keep ventilation openings, in the appliance
enclosure or in the built-in structure, clear of
obstruction.
Optimum room
temperature
+10 ºC to +32 ºC
+16 ºC to +32 ºC
+18 ºC to +38 ºC
+18 ºC to +43 ºC
There must be at least 35 mm clearance
between the base of the appliance and the
floor.
IMPORTANT! There must be free access
to the ventilation grille (fig. 3).
4
fig. 2
fig. 3

Publicidad

loading

Este manual también es adecuado para:

Vt307Vt406Vt407Vt306