Descargar Imprimir esta página

Hisense Hi-Therma Serie Manual De Instalación Y Mantenimiento página 45

Ocultar thumbs Ver también para Hi-Therma Serie:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 83
ELECTRICAL AND CONTROL SETTINGS
9.5 SETTING OF DIP SWITCHES ON PCB1
?
N O T E
• The mark "■" indicates the dip switches positions.
• No mark "■" indicates pin position is not affected.
• The figures show the settings before shipment or after selection.
• "Not used" means that the pin must not be changed. A malfunction
might occur if changed.
!
C A U T I O N
Before setting dip switches, first turn the power supply OFF and then
set the position of dip switches. If the switches are set without turning
the power supply OFF, the contents of the setting are invalid.
(1) DSW1: Unit model setting
No setting is required.
Split
(2) DSW2: Unit capacity setting
No setting is required.
044(2.0 HP)
060(2.5 HP)
(3) DSW3: Additional setting
Setting before shipment
ON: Cancel 70 alarm (Water pressure abnormality)
Anti-freezing settings
ON: Whole water cycle does anti-freezing.
OFF: Only primary cycle does anti-freezing.
(4) DSW4: Additional setting
Setting before shipment
Water pump forced ON
Auxiliary electric heater
forced OFF
ON: Anti-freezing enabled
OFF: Anti-freezing disabled
080(3.0 HP)
7 8
7 8
7 8
7 8
Water pump mode when
Thermo OFF
ON: Operate constantly
OFF: Operate periodically
Manual emergency setting
ON: Manual emergency enabled
OFF: Manual emergency disabled
DHW electric heater allowance setting
ON: DHW electric heater cancel forced OFF
OFF: DHW electric heater forced OFF
DHW 3-way valve forced ON
Start air purge
(5) DSW5: Additional setting
Setting before shipment
ON: Cancel 75/78 alarm (Water pump abnormalities)
ON: WP3 operates in space cooling mode.
(6) DSW6: Fuse reset
Setting before shipment
(7) DSW7: Not used
Setting before shipment
(8) DSW8: Refrigeration system No. setting
Setting is required.
Use binary encoding method. Before shipment are all OFF.
Max No.63 are available to set when all the equipment are
connected to corresponding Central Control System.
Ex: Set refrigeration system No. as 8.
(9) DSW9: Indoor unit No. setting
No setting is required.
Setting before shipment
33
7 8
7 8
7 8
7 8
7 8

Publicidad

loading