Descargar Imprimir esta página

Toshiba MMU-UP0151SH-E Manual De Instalación página 110

Ocultar thumbs Ver también para MMU-UP0151SH-E:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 47
 Remote controller wiring
• 2-core with non-polarity wire is used for the remote controller wiring and group remote controllers wiring.
Remote controller wiring, remote controller inter-unit
wiring
Total wire length of remote controller wiring and
remote controller inter-unit wiring = L + L1 + L2 + ...
Ln
Max. length of each remote control wiring between indoor units = L1, L2, ... , Ln
CAUTION
CAUTION
• The remote controller wire (Communication line) and AC 208 to 240 V wires cannot be parallel to
contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on
the control system due to noise or other factor.
• If U series models (TU2C-Link) are combined with models other than U series (TCC-Link), the wiring specifications
and maximum number of connect-able indoor units will be changed. Pay attentions to their communication
specifications when carrying out the installation, maintenance, or repair. For its details, refer to the "Communication
line" in 7 Electrical connection.
Indoor unit
L
Remote
controller
L1
wiring
Remote
Remote controller inter-unit wiring
controller
Max. number of connect-able indoor units, and communication type
Outdoor unit
U series
Indoor unit
U series
Remote controller
U series
Remote sensor
Communication type
TU2C-Link
Max. number of connect-able
16
units
: Other than U series
REQUIREMENT
After carrying out installation of additional indoor unit, relocation, or repairing, set the addresses again.
For its detail, refer to the Installation Manual attached to the outdoor unit.
217-EN
Wire size: 0.5 to 2.0 mm²
In case of one remote
Up to 500 m
controller
In case of two remote
Up to 400 m
controller
Up to 200 m
Indoor unit
Indoor unit
Indoor unit
L2
Ln
For number of Max. connect-able units,
refer to the following table.
Unit type
U series U series U series
U series
U series U series
U series
U series
TCC-Link
8
– 109 –
 Wiring between indoor and outdoor units
NOTE
A wiring diagram below is an example for connection to SMMS-u series. For connecting to other outdoor unit
series, refer to the Installation Manual attached to the outdoor unit to be connected.
▼Wiring example
Outdoor Power supply
380 - 415 V ~, 50 Hz
380 V ~, 60 Hz
Earth
L1 L2 L3 N
terminal
S: The ground of a
shielded wire
Indoor unit
Earth
U series
Indoor power supply
220 - 240 V~, 50 Hz
208 - 230 V~, 60 Hz
Circuit breaker,
Power switch
Outdoor Power supply
380 - 415 V ~, 50 Hz
380 V ~, 60 Hz
Circuit breaker
Circuit breaker
Outdoor unit
Outdoor unit
Header outdoor
Follower outdoor
Uv
Uh
Uc
Uv
Uh
U1 U2
U3
U4
S U
5
U6
S
Earth
L1 L2 L3 N
U1 U2
U3
terminal
S: The ground of a shielded wire
Control wiring between outdoor units (Shield wire)
Control wiring between indoor and outdoor units (Shield wire)
Control wiring between indoor units (Shield wire)
Indoor unit
Indoor unit
Earth
Earth
L N
Uv(U1) Uv(U2)
A B
L N
Uv(U1) Uv(U2)
A B
A B
A B
Remote controller
Remote controller
Pull box
Pull box
Uc
U4
S U
5
U6
S
Indoor unit
Earth
L N
Uv(U1) Uv(U2)
A B
L N
Uv(U1) Uv(U2)
A B
A B
Remote controller
Pull box
Group control
218-EN

Publicidad

loading

Este manual también es adecuado para:

Mmu-up0181sh-eMmu-up0241sh-e