Descargar Imprimir esta página

Gladiator GCB800 Manual Del Usuario página 10

Publicidad

Idiomas disponibles

Idiomas disponibles

TERMINAL ASS'Y, SHORT ZSI IN
1ea
CONN., 172501-1, AMP
1ea
TERMINAL, 172773-1, AMP
25ea
WIRE ASS'Y OCR types
No.
Drawing No.
Part Name
1
76671176310
WIRE ASS'Y AG AC OCR
2
76671176311
WIRE ASS'Y A ZK PS CKA OCR
3
76671176312
WIRE ASS'Y AE AX PX SX OCR
<Fig. 13 > Components of wire ass'y OCR and types
02
01
03
04
06
05
08
07
10
09
12
11
14
13
16
15
18
17
20
19
Caution
TRIP or OFF STATE
Installation Instructions
Communication, Digital Output, ZSI, Remote Reset
Communication, Digital Output, ZSI, Remote Reset, Earth Leakage(<30A), Voltage Module
Communication, Digital Output, ZSI, Remote Reset, Earth Leakage(>30A), Voltage Module
<Table.3> Terminal Number and Description
Number
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
In case of not using ZSI function
6x13.3 lb-in
Caution
(6x1.5N·m)
<Fig. 14 > Disassembling cover and short connector
- 8 -
WIRE ASS'Y
1ea
Functions
Marking
485+
Comm. +
485-
Comm. -
R1
Power +
R2
Power -
524
Relay Output (Long time)
534
Relay Output (Short time/Instantaneous)
544
Relay Output (Ground fault/PAL)
513
Relay Output Common
Z3
ZSI Out +
Z4
ZSI Out -
Z1
ZSI In +
Z2
ZSI In -
R11
Remote Reset +
R22
Remote Reset -
E1 or B1
Earth Leakage +
E2 or B2
Earth Leakage -
V1
VR Input
V2
VS Input
V3
VT Input
VN
V Input Common
CONN.,172501-1,AMP
TERMINAL ASS'Y, SHORT ZSI IN
No. 11, 12 SHORTED
: If not using ZSI function of Trip Relay (OCR), please short ZSI
INPUT of terminal No.11,12 (ZSI IN +, ZSI IN-) by using the
"TERMINAL ASS'Y,SHORT ZSI IN"
10P CONNECTOR
12P CONNECTOR
OCR Trip Unit Types
A Type
P, S Type
P, S Type
Description

Publicidad

loading

Este manual también es adecuado para:

Gcb1200