Descargar Imprimir esta página

Gladiator GCB800 Manual Del Usuario página 8

Publicidad

Idiomas disponibles

Idiomas disponibles

4. Accessory and Control Wiring Installation
HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION
1) Turn off all power supplying this equipment before working on or inside equipment.
2) Before removing the auxiliary cover in a circuit breaker, make sure there is no voltage present where work is to be performed and circuit breaker is tripped.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR SEVERE INJURY.
1) Remove appropriate tab of safety cover with plier(A).
2) Install safety cover(B).
3) Loosen four screws from the auxiliary cover and open it (C).
4) Install field-installable accessories according to instructions supplied with them.
5) Arrange wire through wire opening in auxiliary cover to avoid pinching wires.
6) Replace auxiliary cover (D), and be careful not to pinch wires when installing cover.
Replace all auxiliary cover screws (E). Do not exceed torque specification of screws.
7) If circuit breaker has factory-installed accessories, refer to label on circuit breaker for electrical specifications.
Installation Instructions
DANGER
Remove
AUX #1, AUX #2, AUX #3
ALM
SHT or
UVT
<Fig. 9> Control Wiring Installation
- 6 -
8Χ18.2 lb-in
(8Χ2.05N·m)
6x13.3 lb-in
(6x1.5N·m)