Display
6) Display of measurement
Relay setting
display
Display
Trip Relay Setting
Button
If pressing 'Up cursor' four times on the Relay setting Display, Instantaneous pick up setting value will be displayed.
× 4
If pressing 'Up cursor' five times on the Relay setting Display, the setting value of Ground-fault pickup will be displayed.
× 5
If pressing 'Up cursor' six times on the Relay setting Display, the setting value of Ground- fault tripping delay will be displayed.
At this time, one larger value than the initial one will be displayed because LSB of time setting value is set in case of l²t is
× 6
On. For example, if it is of l²t 0.400sec on setting, 0.401 will be displayed.
If pressing 'Up cursor' seven times on the Relay setting Display the setting current cursor Display, of ground fault will be displayed.
× 7
At this time, the 10~100% of In will be displayed and other values out of this range will be indicated as "_ _ _ _"
Measurement
display
Communication
Communication
Address setting
Speed set
Button
× 2
If pressing 'MENU' button 3 times from the measurement Display, move to Communication Address Setting screen.
Communication Address can be set from 1 to 247.
Press Enter button to save the setting, otherwise press ESC/RESET button to move back to Measurement Display.
If successfully saved, 'SAVE' is displayed on screen and move to Measurement Display and if pressing ESC/RESET
button, move to Measurement Display without saving.
If pressing 'MENU' button 3 times from measurement Display screen, move to Communication Speed Setting screen.
× 3
Communication speed can be set through Baud rate 38400 / 19200 / 9600.
If pressing 'Up / Down'cursor, the value of Baud rate rolling over will be displayed.
Press Enter button to save the setting, otherwise press ESC/RESET button to move back to Measurement Display.
If successfully saved, 'SAVE' is presented on screen and move to Measurement Display and if pressing ESC/RESET
button, move to Measurement Display without saving.
If pressing 'MENU' button 4 times from Measurement Display, move to Present Time Display.
The present time is displayed with 'hour' and 'minute' by 24H type and Dot between hour minute hour and minute turns
× 4
on and off every second. Unless present time is set, present time will be set '1 hour 1minute' as initial time is set as '1hour
1minute 1 second January 1st, 2000'.