1) Solution for Circuit Breaker's abnormal condition
Type
Condition
Terminal unit
Temperature
Overheating
Increase
Product (except terminal unit)
overheating
Impossibility of closing (ON)
Abnormal
Impossibility of reoperating
operation
Impossibility of Breaking
/ OFF Impossibility
Fault
Current
Fault Current Flow
Flow
Break
On normal load breaking
Fault operating
During
motor starting
Frequent
MCCB's
Instantaneous
Operation
While Starting
Operating current
Inactivity
of rated current
Short circuit of
Inactive operation
Power side
over rated operating current
2) Solution for accessories abnormal operation
Type
Condition
SHT
Trip inactive
UVT
Closing impossible
ALM/AUX
Fault operation
Installation Instructions
Possible Causes
 Loose terminal unit tightening screw
 Faulty busbar bar assemble
 Faulty contact to internal contactor
 Current density increase by wire terminal
 Foreign substance in switch
 Reclosing without reset on trip position
 Worn out by breaking endurance
 Reset device operation fault
 The coil of under voltage trip device is not excited.
 Switch spring burn out and exhaustion.
 Bimetal corrosion and transformation
 Reaching the life of switch limit
 Overheating of over current detecting element
 Contact meeting and fusion by excessive breaking current
 Inflow of insulation material between contact.
 Conductive unit melting
 Contact burn out (wear)
 Wrong selection of product rating (causing overheating)
 No window inside panel (Causing overheating)
 MCCB internal heating
 Loose terminal connection unit.
 Heating by starting current
 Overload current more than rated current flows.
(when using motor with overload or over voltage)
 Excessive starting current
 Excessive current Y△ starting switching
 Excessive current by reversible operation
 Instantaneous restarting rush current
 Operation by starting current like charging current of condenser,
incandescent electric lamp flow, charging, etc.
 Motor's Layer Short
 Abnormal current flow at the same time with closing
 Operating circuit fault connection
 Large rated current
 Current limit break of top fuse or incompatibility with top circuit breaker
 Dust piling up
 Switch side drop away of conductive material
Possible Causes
 Operating voltage drop
 Incorrect commercial voltage selection
 Coil burn out
 Applied frequency or voltage fault
 Loose attachment screw
- 11 -
GCB800/1200
Solution
 Tightening with designated torque
 Busbar bar reassemble
 New product replacement
 Remove foreign substance
 Closing after reset
 New product exchange
 Request after service
 Applying power
 Replacement and mending
 Request after service
 New product exchange
 Operating after cooling
 New product exchange
 Remove foreign substance
 New product exchange
 New product exchange (rating reselect)
 New product exchange
 Tightening terminal screw (check)
 New product exchange
 Rating adjustment
 Instantaneous breaking current setting or rating adjustment
 Motor mending
 Circuit inspection
 Select low rated current
 Protection cooperation review or rating adjustment
 New product exchange
 New product exchange
Solution
 Power improvement
 Request after service
 Power improvement
 Readjustment