4.3 OPERATING MODES OF THE HMIR
The HMIR must be configured via hardware on S10 DIP-switch before the operation. The S10
DIP-switch is shown in
recognizing the HMIR the inverter can be adjusted as shown in
ID
S10.1
S10.2
0
OFF
1
OFF
2
OFF
3
OFF
4
OFF
5
OFF
6
OFF
7
OFF
8
ON
9
ON
10
ON
11
ON
12
ON
13
ON
14
ON
15
ON
The monitoring mode allows the user to view up to three variables on the main display, secondary
display and bar graph. Such fields of the display are defined in
The setting mode is composed of three levels: Level 1 allows the user to select the Menu items in
order to browse the parameters. Level 2 allows browsing the parameters of the group selected
by level 1. Level 3 allows the modification of the parameter selected in Level 2. At the end of
this level, the modified value is saved or not if the key ENTER or ESC is pressed, respectively.
Figure 4.3 on page 26
illustrates the basic browsing of the operating modes of the HMIR.
Figure A.2 on page 199
Table 4.1: S10 DIP-switches configuration
S10.3
S10.4
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
Keypad (HMIR) and Basic Programming
of
APPENDIX A - PARTS on page
Table 4.1 on page
Power-Up Function
None
Load 50 Hz factory parameter table standard
Load 60 Hz factory parameter table standard
None
None
None
None
None
Force HMI serial protocol
Force Modbus RTU serial protocol
None
None
None
None
None
None
Figure 4.2 on page
198. For
25.
24.
MW500 | 25