Technical Specifications
8.2 ELECTRONICS/GENERAL DATA
Control
Method
Output frequency
Performance
V/F control
VVW
Sensorless
Vector with encoder
Inputs
Analog
(*)
Digital
Outputs
Relay
(*)
Transistor
Power supply
Communication
Interface RS485
Safety
Protection
Human-machine
Remote keypad
interface (keypad)
(HMIR)
Enclosure
Degree of
protection
(*) The number and/or type of analog/digital inputs/outputs may vary, depending on the Plug-in module (accessory) used. For the table above, it was
considered the standard plug-in module. For further information, refer to the programming manual and the guide supplied with the optional item.
(**) The maximum capacity of 150 mA must be considered by adding the load of the 24 V power supply and transistor output, that is, the sum of the
consumption of both must not exceed 150 mA.
46 | MW500
Table 8.1: Electronics/general data
Type of control:
- V/f (Scalar)
- V V W: Voltage vector control
PWM SVM (Space Vector Modulation)
0 to 500 Hz, resolution of 0.015 Hz
Regulation (with slip compensation): 1 % of the rated speed
Speed variation range: 1:20
Regulation: 1 % of the rated speed
Speed variation range: 1:30
Regulation: 0.5 % of the rated speed
Speed variation range: 1:100
Regulation: 0.1 % of the rated speed with a digital reference (keypad, serial,
dieldbus, Electronic Potentiometer, Multispeed)
Knob additional input for speed reference variation
1 insulated input. Levels: (0 to 10) V or (0 to 20) mA or (4 to 20) mA
Linearity error ≤ 0.25 %
Impedance: 100 kΩ for voltage input, 500 Ω for current input
Programmable functions
Maximum voltage permitted in the input: 30 Vdc
4 insulated inputs
Programmable functions
- active high (PNP): maximum low level of 15 Vdc
minimum high level of 20 Vdc
- active low (NPN): maximum low level of 5 Vdc
minimum high level of 9 Vdc
Maximum input voltage of 30 Vdc
Input current: 4.5 mA
Maximum input current: 5.5 mA
1 relay with NC/NO contact
Maximum voltage: 240 Vac
Maximum current: 0.5 A
Programmable functions
1 insulated digital output open sink (uses as reference the 24 Vdc power
supply)
Maximum current 150 mA
(**)
Programmable functions
24 Vdc power supply. Maximum capacity: 150 mA
10 Vdc power supply. Maximum capacity: 2 mA
Insulated RS485
Modbus-RTU protocol with maximum communication of 38.4 kbps
Overcurrent/phase-phase short circuit in the output
Overcurrent/phase-ground short circuit in the output
Under/overvoltage
Overtemperature in the heatsink
Overload in the motor
Overload in the power module (IGBTs)
External alarm / fault
Setting error
9 keys: Start/Stop, up arrow, down arrow, Direction of Rotation, Jog, Local/
Remote, BACK/ESC and ENTER/MENU
LCD display
View/edition of all parameters
Indication accuracy:
- current: 5 % of the rated current
- speed resolution: 0.1 Hz
IP66
UL type 4X
(maximum capacity of the 24 Vdc) power supply