Using a fork spanner SW 7 screw the
►
union nuts SW 30 (3) and the screw-in fit-
tings M 7 (1) together (tightening torque
30 Nm). In doing so, alternatingly tighten
just 1– turns in each case to prevent the
threaded connection part from jamming.
Attach panels (4).
►
Transport radiator only in a standing position.
►
Install built-into-wall brackets (see Fig. 1–8)
Observe submersible radiator-wall spacing
►
(WA) (see Fig. C).
In the event of a projection from the wall,
e.g. insulation material, the projecting
length of the built-into-wall bracket is re-
duced by the thickness of the projection (see
Fig. 4).
Prepare tools.
►
Drill holes. Note walling material.
►
Note: Brackets with lift restraints are installed
on top, outside and possibly additionally even-
ly spaced along the length.
Pre-install lift restraints.
►
Install built-into-wall brackets:
►
Note the orientation of the built-into-
–
wall bracket, slit to the top.
Make sure that the built-into-wall brack-
–
et's expansion zone is not completely
within a hollow space of the building
material used.
Align and secure the built-into-wall brackets.
►
Shorten panel if required and attach with
►
the raw edge to the wall.
Attach rosette.
►
For BH 1050: Install spacers (see Fig. 9–10).
Depending on the installation situation,
►
use spacer extensions as necessary.
Installing and securing the radiator (see
Fig. 11–13)
Place the radiator with the straps into the
►
brackets and align laterally.
Clamp the lift restraints over the radiator
►
straps.
Align radiator.
►
Standard version connection
Vent plugs (top) and blind plugs are factory
pre-assembled.
Unscrew painted blind plugs at the desig-
►
nated connection points.
Connect radiator with commercially avail-
►
able fittings upstream.
6
Tightly cap open connections with vent
►
plugs (top) and blind plugs.
Connection version with built-in valve
Valve with factory pre-set k
facturer's data).
Vent plugs (top) and blind plugs are factory
pre-assembled.
Remove painted caps on the valve mount-
►
ings and dispose of, as they must not be
used as seals on the radiator.
Connect radiator with commercially avail-
►
able fittings upstream on the valve mount-
ings.
Special connections
See manufacturer's data.
►
Commissioning
Remove protective packaging completely
►
during final cleaning or prior to commis-
sioning.
►
Fill the radiator and evacuate the air from it
via the air vent. Risk of scalding!
Check radiator and connections for leaks.
►