Installation Guide
Floor stand Installation
Bottom Bracket
(3-Bay Charger)
Bottom Bracket
(5-Bay Charger)
Pogo Stick
Mounting Hole
Fig. 6 – Floor Stand
Webasto Charging Systems, Inc.
DANGER
CONNECTION TO MAIN POWER
•
Only qualified service personnel should remove the cover.
•
Only a qualified electrician is to make electrical connections!
•
Make sure that the service AC input voltage is powered off before
wiring the charger.
•
This device does not contain any user serviceable parts.
DANGER
CONNECTION TO MAIN POWER
•
Ensure that the AC power cables to be used are disconnected from
the AC power supply before continuing!
•
Verify that there is no connection to the AC before opening the cabinet,
which exposes AC wiring, and making terminal connections!
•
Disconnect all power before servicing!
WARNING
RISK OF FIRE
•
Use VAC input (indicated above) only on circuits with a branch circuit
protection in accordance with the NEC NFPA 70 to reduce the risk of fire.
•
These circuits (maximum CB size) also are to be consistent with the
supply current (input amps) indicated in section 2 for the respective
number (2–5) and voltage (48V or 80V) of fitted modules and cabinet
size (3 or 5 bays).
•
Ensure that the AC wiring (minimum AC input wire size [AWG]) indicated
in section 2 to meet NEC requirements.
•
Refer to section 2 also for AC input voltage specifications.
Fig. 7 – Predrilled
Holes for Bolting
Base to Floor
Fig. 8 –
Optional Pogo Stick
VAC Input
3-phase 480VAC
Page 9 of 12
ProCore Edge North America
Fig. 9 –
Charger on
Floor Stand
Fig. 10 – Bottom
Bracket M5 Screw
31241-76-0104