I/O module (optional expansion module)
Input/output
6 floating relay outputs (changeover)
3 digital inputs 230 V AC
3 digital inputs 24 V AC
2 analogue outputs, to be set using jumpers
0 V – 1 V or 2 V – 10 V
0 mA – 20 mA or 4 mA – 20 mA
Interfaces to the controller
RS-485
19.2 kbit/s
Floating
connection with plug or screw terminals
RSI-specific protocol
5.2
Settings
GEFAHR
Danger to life from electric shock!
Risk of serious injury or death due to electric shock. Some parts of the main
board may still be at a voltage of 230 V even after the mains plug has been
pulled out.
Before you remove the covers, completely isolate the device controller
from the power supply.
Verify that the main circuit board is voltage-free.
5.2.1
Terminator settings in RS-485 networks
Examples for the activation and deactivation of terminators in RS–485 networks.
The main circuit board of the Control Basic provides either the DIP switches
1 and 2 or the jumper J3.
Maximum length for an RS–485 connection is 1000 metres
Device controller with I/O module
1
Relay outputs of the I/O
module
6 digital outputs
2 analogue outputs
2
I/O module
3
Connections of the I/ O
conductors
Terminator settings
Jumper / Switch
Settings
Jumper J10
Activated
and J11
Deactivated
DIP switch 1
Activated
and 2
Deactivated
Jumper J3
Activated
1 and 2 as well as
3 and 4
Deactivated
30 — English
4
"Control Basic" controller
5
RS-485 connection
6
Optional RS-485 connection
Master - Slave
Field bus
I/O module
Control Basic
X
---
---
---
---
X
---
---
---
X
---
---
Variomat Basic — 09.09.2022-Rev. C
Device controller with I/O module and bus module
I/O module
1
2
Bus module
Terminator settings
Jumper /
Settings
Switch
Jumper J10
Activated
and J11
Deactivated
DIP
Activated
switch 1
and 2
Deactivated
Jumper J3
1 and 2 as
Activated
well as
3 and 4
Deactivated
Device controllers and I/O module in Master-Slave function
Control Basic controller in
1
Master function
2
I/O module for the Master
function
Master function
Terminator settings
Jumper /
Settings
Switch
Jumper J10
Activated
and J11
Deactivated
DIP switch 1
Activated
and 2
Deactivated
Jumper J3
Activated
1 and 2 as well
as
3 and 4
Deactivated
Slave function
Terminator settings
Jumper /
Settings
Switch
Jumper J10
Activated
and J11
Deactivated
DIP switch 1
Activated
and 2
Deactivated
Jumper J3
1 and 2 as
Activated
well as
3 and 4
Deactivated
3
"Control Basic" controller
I/O module
Control Basic
Bus module
Lon Works
Profibus DP
Ethernet
---
---
X
---
---
X
---
---
---
X
---
---
Control Basic controller in
3
Slave function
4
I/O module for the Slave
function
I/O module
Control Basic
X
---
---
---
---
X
---
---
---
X
---
---
I/O module
I/O module
Control Basic
for expansion
---
X
X
---
---
---
---
---
---
---
---
---
---
---
---
---
X
---
---
---
X
---
X
---