Installation
3
Overflow valve (not for motor
ball valve)
4
Group message
5
Optional for second pressure
value
6
Motor ball valve (control
connection)
7
RS-485 interface
8
Shielding
Terminal
Signal
number
1
PE
230 V voltage supply via mains
2
N
cable and plug.
3
L
4
PE
5N
N
Pump for pressure maintenance.
6 M1
M 1
7
Y2
Overflow solenoid valve
8
N
•
9
PE
10
Y 1
11
N
Valve for control of water make-up. Pre-wired
12
PE
13
COM
Group message (potential free).
14
NC
Max. 230 V, 2 A
15
NO
16
Not assigned
External make-up request.
17
Make-up (230
•
V)
18
Make-up (230
V)
19
PE shield
Level analogue input.
•
20
- Level (signal)
•
21
+ Level
•
(+ 18 V)
22
PE (shield)
Pressure analogue input.
23
- Pressure
•
(signal)
•
24
+ Pressure
(+ 18 V)
25
0 – 10 V
(correcting
variable)
Motor ball valve in the overflow
26
0 – 10 V
line to actuation the pressure
(feedback)
maintenance.
27
GND
28
+ 24 V (supply)
29
A
30
B
RS-485 interface.
31
GND
+ 24 V (supply)
Supply for E1 and E2.
32
E1
Max. 230 V, 2 A
E1
Contact water meter (in Fillset, for
example)
•
33
•
38 — English
11 Pressure analogue input
12 External make-up request
13 Make-up valve
14 Pump "PU"
15 Mains supply
Function
Wiring
Pre-wired
Pre-wired
---
Not used in a standard
device.
On-site,
optional
To be used only upon
---
consultation with the Reflex
Customer Service.
Factory
prepared,
For output to the display.
sensor plug
Actuation of the make-up.
must be
To protect the pump from dry
inserted on-
run protection.
site
For output to the display.
Pre-wired
Actuation of pressure
maintenance.
Pre-wired
On-site,
optional
Pre-wired
On-site,
Analysis of the make-up.
optional
If contact 32/33 is closed =
meter pulse.
Variomat Basic — 09.09.2022-Rev. C
Terminal
Signal
number
E2
Low water switch.
•
34
•
Max. 230 V, 2 A
7.5.2
RS-485 interface
Use the S1 and S2 RS-485 interfaces to retrieve all controller data and to enable
the communication with control centres or other devices.
•
S1 interface
–
A maximum 10 devices can be used in a master-slave linked circuit
via the this interface.
•
S2 interface
–
"PIS" pressure and "LIS" level.
–
Operating modes of the "PU" pumps.
–
Operating states of the motorised ball valve/solenoid valve.
–
Values of the "FQIRA +" contact water meter.
–
All messages.
–
All entries in the fault memory.
The following bus modules form part of the optional accessories available for
interface communication.
Note!
If required, please contact the Reflex Customer Service for the protocol
of the RS-485 interface, details of the connections and information about
the accessories offered.
7.5.2.1
Connecting the RS-485 interface
Circuit board of the Control Basic controller.
1
DIP switch 1
Proceed as follows:
1.
Open the housing cover of the Control Basic controller.
2.
Use a screened cable to connect the RS-485 interface to the main circuit
board.
•
Terminal 29 (A+)
•
Terminal 30(B-)
•
Terminal 31(GND)
3.
Connect the cable screen at one side.
•
Terminal 22
4.
Activate the terminators on the main circuit board.
•
Dip switch 1
Note!
Activate the terminator when the device is at the beginning or the end
of an RS-485 network.
7.6
Installation and commissioning certificate
Note!
The installation and commissioning certificate can be found at the end
of the operating manual.
Function
Wiring
Not used in this device.
---
If contact 32/34 is closed =
OK.
2
Connection terminals for RS-
485 connection