Modbus
Choose your options. MODBUS RTU (RS485)
PARAMETER
Code
Default
Unit address
CF30
16
Baud rate
CF31
19200
Parity
CF32
2
Parity: 0=NONE; 1=ODD: 2=EVEN;
Baud rate
0
9600
3
57600
1
19200
4
76800
2
38400
5
115200
Touch
to go ahead. MODBUS TCP/IP
Choose your options.
Touch
to go ahead.
Choose your options.
Switch off /switch ON the dryer
to confi rm
English
Condensate drain
Touch
to enter.
Touch as indicated to choose the type of the drain:
0 = external;
1 = timed;
2 = capacitive.
in the case of the choice of the timed discharger (1) it is also possible to choose the closing and ope-
ning times "D1 / D2".
Maintenance
Touch
to enter.
these data are read-only.
PSE 325-1000 60Hz
14/20