ADDRESS SETUP
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor electric wiring work and unpracticed outdoor
electric wiring work (Manual setup from wired remote controller)
Arrange indoor unit in which address
is set up and the wired remote controller to 1 : 1.
(Cabling example in 2 lines)
Line 1
Outdoor
Indoor
Remote
controller
Header
1
Line address
1
2
Indoor address
1
2
Group address
1
In the above example, under condition of
no inter-unit wire of the wired remote
controller, set the address after individual
connecting of the wired remote controller.
Group address
Individual
: 0000
Center unit
: 0001
}
In case of group control
Terminal unit : 0002
Operation procedure
1
2
3
4
7
8
9
10
Data
11
1
4, 7, 10
Line 2
(Line address) → → → → →
Follower
1
2
2
3
1
2
2
2
2
(Indoor address) → → → → →
(Group address) → → → → →
5
6
11
End
CODE No.
SET DATA
UNIT No.
R.C.
No.
UNIT
SET
CL
Turn on the power.
1
Push simultaneously
for 4 seconds or more.
LCD changes to flashing.
2
Using the setup temp.
12
set
to the item code.
3
Using the timer time
the line address.
(Match it with the line address on the interface P.C.
board of the header unit in the identical refrigerant line.)
4
Push
button.
SET
(OK when display goes on.)
5
Using the setup temp.
13
set
to the item code.
6
Using the timer time
the indoor address.
7
Push
button.
SET
(OK when display goes on.)
8
Using the setup temp.
14
set
to the item code.
9
Using the timer time
0000
Individual =
0002
Follower unit =
10
Push
button.
SET
(OK when display goes on.)
11
Push
button.
Setup operation finished.
(Status returns to normal stop status.)
Item code
3, 6, 9
2, 5, 8
15
+
+
SET
CL
/
/
buttons, set up
/
/
buttons, set up
/
/
buttons, set
0001
, Header unit =
.
buttons
buttons,
buttons,
buttons,
,