4 Technical data
4.3
Outputs
4.3.1
Analog outputs
Current output
Signal range
Output signal limits
Accuracy
Temperature influence
Burden influence
Burden
Voltage output
Signal range
Output signal limits
Accuracy
Temperature influence
Load influence
Load
4.4
Interfaces
RS485
Galvanic isolation
Data transmission
Data format
Transmission protocol
Data transfer rate
Function
a
Default setting
USB
Transmission standard
Connector type
Power requirement
Cable length
Function
10
4 to 20 mA
0 to 22 mA
≤±0.05 % in relation to the end of the signal range (20 mA)
±50 ppm/K
≤±0.02 % per 100 Ω
≤ 500 Ω
0 to 10 V
0 to 11 V
≤ ±0.05 % in relation to the end of the signal range (10 V)
50 ppm/K
≤±15 mV
≥ 10 kΩ
Functional
Serial
a
8-1-none
8-1-odd
8-1-even
8-2-none
Modbus RTU
9600 baud
19200 baud
a
38400 baud
57600 baud
115200 baud
Transfer of process data, configuration data, and device information
USB 2.0
Micro-B
≤ 500 mA
≤ 5 m
Transfer of configuration data and device information