baltur COMIST 180 Manual De Instrucciones página 57

Quemadores mixtos gas / gasóleo
Ocultar thumbs Ver también para COMIST 180:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTRUCTIONS FOR SETTING
DUNGS GAS VALVES
mod. MVD ... and MVDLE ...
The MVD gas valves open and close rapidly.
To regulate the gas flow, unscrew and remove cap "A" and loosen
nut "B".
Then, using a screwdriver turn screw "C". Unscrewing it increases
the gas flow, tightening it decreases the flow.
After regulating, lock nut "B" in place and reposition cap "A".
HOW THE VALVE FUNCTIONS mod. MVDLE
The gas valve has a rapid initial trip (opening can be adjusted from
0 to 40% using pin "G"). Full opening from that point on takes place
slowly over approximately 10 seconds.
N.B. There will not be sufficient supply for ignition if the flow feed
device "E" is set at its minimum position. Therefore, it is
essential to open the maximum flow rate control device "E"
sufficiently to ensure ignition.
Setting the initial rapid release trip
To set the initial rapid release, unscrew the protection cap "F" and
use the back of this cap as a tool to turn pin "G".
Turning clockwise decreases the gas flow, turning counter-clockwise
increases it.
This done, return cap "F" to its original position.
Setting maximum gas flow
To adjust the gas flow rate, loosen screw "D" and turn knob "E".
Turning clockwise decreases the gas flow, turning counter-clockwise
increases it.
This done, tighten screw "D".
N° 8875
Rev. 06/11/90
19 / 34
0006080095_200902
Mod. MVD....
D = Identification plate
E = Flow direction indicator
Mod. MVDLE....
H = Identification plate
I
= Flow direction indicator
E
N
G
L
I
S
H

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Comist 250Comist 300

Tabla de contenido