Descargar Imprimir esta página

Tripp-Lite SmartOnline SUINT1500LCD1U Manual Del Propietário página 21

Sistemas ups monofásicos 100% en línea de 1u con salida de onda sinusoidal pura

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 32
6 Operation
Notes:
1. Refer to section 2.5 Operation Panel for operation panel indicators and meanings.
2. Refer to section 2.6 Rear Panel and section 7. Communication Interfaces to understand how to use the UPS interfaces.
6.1 Start-Up Procedures
To turn on the UPS, press and hold the On button
6.2 Cold-Start
Even when there is no utility power, you can still turn on the UPS. Press and hold the On button
it after you hear one beep and the UPS will start up and run in Battery Mode.
6.3 Shutdown Procedures
1. In any of the protected operating modes, press and hold the OFF button
beep. The UPS will switch to Off Mode and the UPS will provide either bypass output or no output, depending on the Off-
Mode Bypass Output user configuration.
The UPS will keep charging the batteries with the UPS in Off Mode. To power the UPS completely off, disconnect the AC
power cord from utility power when the UPS is in Off Mode.
2. To turn off the UPS in Battery Mode, press and hold the Off button
The UPS will turn off its output.
6.4 Setup Menu
Press the scrolling buttons
Please note that only qualified service personnel can perform setup actions. In Setup Mode, the following items can be set up:
Alarm Mute
Power Strategy
for 3 seconds and release it after you hear one beep.
for more than 3 seconds and the LCD will enter the setup menu.
for 3 seconds. Release it after you hear one
for 3 seconds. Release it after you hear one beep.
Selectable Options:
Alarm Mute On - Alarm is disabled
Alarm Mute Off - Alarm is enabled (Default)
Selectable Options:
AdA: Auto Adaptive (Default)
qUA: Max. Quality (Normal On-Line Mode)
EFF: Max. Efficiency (ECO Mode)
FC5: Frequency Conversion 50 Hz
FC6: Frequency Conversion 60 Hz
FCA: Frequency Regulation (Constant Frequency
Auto-select 50/60 Hz)
21
for 3 seconds. Release

Publicidad

loading

Este manual también es adecuado para:

Smartonline suint2000lcd1uAg-03acAg-0569