INSTALLATION
INSTRUCTIONS
21
Connecfing
elecfric
dryers
(conf.)
USA
only
AWARNING
. Connect the power cord to the terminal
block. Each colored
wire should be connected
to same color screw. Wire color
indicated
on manual
is connected
to the same color screw
in block. Failure to follow
these instructions
may result
in a
short or overload.
. Grounding through the neutral conductor is prohibited
for: (1) new branch-circuit installations, (2) mobile homes,
(3) recreational vehicles, and (4) areas where local codes
prohibit grounding through the neutral conductor.
_
our-Wire
Connection
for Electric
Dryers:
Power
Cord
. A 4wire
connection
is required for all mobile and manufactured
home installations,
as well as all new construction
after January 1,
1996.
. A UL-listed
strain relief is required.
1. Remove the terminal
block access cover on the upper back of
the dryer. Install a UL-listed
strain relief into the power cord
through-hole;
then thread a Ul_-Iisted, 30 A, 240 V, 4-wire,
#10
AWG-minimum
copper conductor
power cord through
the
strain reliefl
iiil
_UL-,sted
_
Strain Relief
UL-Listed
/
4-Wire Power
Cord
. Use a 30 A, 240 V, UL-listed power cord with #10 AWG-
minimum
copper
conductor
and closed loop or forked
terminals
with upturned
ends.
2. Transfer the dryer's ground wire from behind the green ground
screw to the center screw of the terminal
block. Attach the two
hot leads of the power cord to the outer terminal
block screws.
Attach the white neutral wire to the center terminal
block
screw. Attach the power cord ground wire to the green ground
screw. TIGHTEN ALL SCREWS SECURELY. Reinstall the terminal
block access cover.
Hot
Ground
Screw
Neutral
.......
- (White)
............ _
Hot
ted)
Ground
Wire