Reinforced insulation separates the output terminals from other circuits. Users can also connect circuits that are not
Safety Extra-Low Voltage circuits if the drive output is 250 Vac 1 A maximum or 30 Vdc 1 A maximum.
*5
Set L8-05 = 1 [Output Phase Loss Protect Select = Enabled] or set the wiring sequence to prevent input phase loss.
Wire Selection
Select the correct wires for main circuit wiring.
Refer to
Main Circuit Wire Gauges and Tightening Torques (for CE Standards) on page 266
wire gauges and tightening torques as specified by European standards.
Control Circuit Wire Gauges and Tightening Torques
Table 1.3 Control Circuit Wire Gauges and Tightening Torques
Termi
nal
Terminal
Block
TB1-1 PS, S1 - S7, SN, SC, SP
AM, AC, A1, A2, +V, H1, H2,
TB1-2
HC
TB1-3 MP, RP, AC, D+, D-, P1, C1, P2,
C2
TB2
MA, MB, MC
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to
external dimensions and model numbers of the crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions
Table 1.2 Icons to Identify Screw Shapes
Icon
Recommended
Gauge
mm
2
(AWG)
0.75
(18)
0.75
(18)
Figure 1.7 External Dimensions of Crimp Ferrules
+/-
Slotted (-)
Hex socket cap (WAF: 5 mm)
Bare Wire
Applicable
Gauge
mm
2
(AWG)
• Stranded wire
0.25 - 1.0
(24 - 17)
• Solid wire
0.25 - 1.5
(24 - 16)
• Stranded wire
0.25 - 1.5
(24 -16)
• Solid wire
0.25 - 1.5
(24 - 16)
Table 1.4
Screw Shape
Crimp Ferrule
Recommended
Applicable
Gauge
Gauge
mm
2
(AWG)
mm
0.5
0.25 - 0.5
(20)
(24 - 20)
0.5
0.25 - 1.0
(20)
(24 - 17)
for the recommended
1 English
for
2
(AWG)
21