PRESSURE SENSOR CALIBRATION
To calibrate the pressure sensor, provide:
- A ZERO value (system with zero pressure)
- A reference value (e.g. system with 5 bar)
It is necessary to have:
- An auxiliary manometer on the same delivery circuit of the inverter
- Operate the pump (open a tap)
To access calibration, starting from INVERTER in STAND-BY
P 3,5
Inverter in
Switch off
STAND-BY
calibration
SP 0.0
If P in system
= 0
asks for the
I confirm
ZERO bar
with SET
reference
Increase the pump speed until the set reference pressure is
reached on the pressure gauge
MAINTENANCE
Display Off
Wait 30 sec
Switch on
again
SP 5.0
If the pump does
NOT reach 5 bar
Reduce the
asks for the
5.0 bar
reference
reference
pressure
=
SP 5.0
STARTING
Within 10 sec
 
During the STARTING phase (10 sec) press the 4
arrows SIMULTANEOUSLY
Open a tap
I confirm the
reference
pressure
46
START
/stop
Start the
Check the
pump
pressure in
the system
OFF
Calibration
performed