Alarm for the pH/ORP Set Point
When the alarm band is set, a work window is created. If the allowed limits are exceeded the alarm relay closes
and remains closed until the measurement is reset or
When the OFA time (Over Feed Alarm) is set, the dosing time of Set Point pH/ORP in time is controlled with two
alarms:
 First alarm at 70% of the time set is seen on the display, the alarm relay closes.
 Second alarm at 100% of the time set is seen on the display and the alarm relay closes and the
pH/ORP pump is blocked.
Press
(3 seconds) to reset OFA Alarm or press
ALR Band
Set Point pH
ALR Band
Pump pH
ALR Relay
(*
1
Measure alarm Ranges - fixed values)
n
1
Temp. Measure min
2
Temp. Measure Max
3
pH Measure
min
4
pH Measure
Max
5
ORP Measure min
6
ORP Measure Max
7
CL Measure
min
8
CL Measure
Max
0000138994
Item
rev. 3.2
is pressed to deactivate the alarm.
(5 seconds) to reset OFA Alarm.
+ 10°C
+ 38°C
6 pH
8 pH
+ 600 mV
+ 800 mV
0,50 ppm
2 ppm