SAFE2 logic= 0 - Input configured as Phot (photocell) non tested (*). (fig.S, ref.1).
Enables connection of devices not equipped with supplementary test contacts. When beam is broken, photocells are active during both opening and closing. When beam is broken
during closing, movement is reversed only once the photocell is cleared. If not used, leave jumper inserted.
SAFE2 logic= 1 - Input configured as Phot test (tested photocell). (fig.S, ref.2).
Switches photocell testing on at start of operation. When beam is broken, photocells are active during both opening and closing. When beam is broken during closing, movement is
reversed only once the photocell is cleared.
SAFE2 logic= 2 - Input configured as Phot op (photocell active during opening only) non tested (*). (fig.S, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during closing. During opening, stops
motion for as long as the photocell beam stays broken. If not used, leave jumper inserted.
SAFE2 logic= 3 - Input configured as Phot op test (tested photocell active during opening only (fig.S, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during closing. During opening, stops motion for as long as the photocell beam stays broken.
SAFE2 logic= 4 - Input configured as Phot cl (photocell active during closing only) non tested (*). (fig.S, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during opening. During closing, movement
is reversed immediately. If not used, leave jumper inserted.
SAFE2 logic= 5 - Input configured as Phot cl test (tested photocell active during closing only (fig.S, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during opening. During closing, movement is reversed immediately.
SAFE2 logic= 6 - Input configured as Bar (safety edge) non tested (*). (fig.S, ref.3).
Enables connection of devices not equipped with supplementary test contacts. The command reverses movement for 2 sec.. If not used, leave jumper inserted.
SAFE2 logic= 7 - Input configured as Bar (tested safety edge (fig.S, ref.4).
Switches safety edge testing on at start of operation. The command reverses movement for 2 sec.
SAFE2 logic= 8 - Input configured as Bar 8k2 (fig.S, ref.5). Input for resistive edge 8K2.
The command reverses movement for 2 sec.
SAFE2 logic=9 Input configured as Bar op, safety edge with active inversion only while opening, if activated while closing, the automation stops (STOP) (Fig. D, ref. 3).
Allows connecting devices not fitted with supplementary test contact. The operation while opening causes the movement to be reversed for 2 seconds, the operation while closing causes
the automation to stop. If not used, leave jumper inserted.
SAFE2 logic=10 Input configured as Bar op test, safety edge checked with active inversion only while opening, if activated while closing, the automation stops (STOP) (Fig. D, ref. 4).
Activates testing safety edges when starting operation. The operation while opening causes the movement to be reversed for 2 seconds, the operation while closing causes the auto-
mation to stop.
SAFE2 logic=11 Input configured as Bar 8k2 op, 8k2 safety edge with active inversion only while opening, if activated while closing, the automation stops (STOP) (Fig. D, ref. 5).
The operation while opening causes the movement to be reversed for 2 seconds, the operation while closing causes the automation to stop.
SAFE2 logic=12 Input configured as Bar cl, safety edge with active inversion only while closing, if activated while opening, the automation stops (STOP) (Fig. D, ref. 3).
Allows connecting devices not fitted with supplementary test contact. The operation while closing causes the movement to be reversed for 2 seconds, the operation while opening causes
the automation to stop. If not used, leave jumper inserted.
SAFE2 logic=13 Input configured as Bar cl test, safety edge checked with active inversion only while closing, if activated while opening, the automation stops (STOP) (Fig. D, ref. 4).
Activates testing safety edges when starting operation. The operation while closing causes the movement to be reversed for 2 seconds, the operation while opening causes the auto-
mation to stop.
SAFE2 logic=14 Input configured as Bar 8k2 cl, safety edge with active inversion only while closing, if activated while opening, the automation stops (STOP) (Fig. D, ref. 5).
The operation while closing causes the movement to be reversed for 2 seconds, the operation while opening causes the automation to stop.
SAFE1 logic= 1 - Input configured as Phot test (tested photocell). (fig.S, ref.2).
Switches photocell testing on at start of operation. When beam is broken, photocells are active during both opening and closing. When beam is broken during closing, movement is
reversed only once the photocell is cleared.
SAFE1 logic= 5 - Input configured as Phot cl test (tested photocell active during closing only (fig.S, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during opening. During closing, movement is reversed immediately.
(*) If "D" type devices are installed (as defined by EN12453), connect in unverified mode, foresee mandatory maintenance at least every six months.
• Launch an autoset operation by going to the relevant menu.
• As soon as you press the OK button, the ".... .... .... " message is displayed and the control
unit commands the device to perform a full cycle (opening followed by closing), during
which the minimum torque value required to move the leaf is set automatically.
The number of cycles required for the autoset function can range from 1 to 3.
During this stage, it is important to avoid breaking the photocells' beams and not
to use the START and STOP commands or the display.
Pressing the + and - keys at the same time during this stage stops the automated
device and exits the autoset operation, with the message KO appearing on the
display. Once this operation is complete, the control unit will have automatically
set the optimum torque values. Check them and, where necessary, edit them as
described in the programming section.
WARNING!! Check that the force of impact measured at the points
provided for by standard EN 12445 is lower than the value laid down
by standard EN 12453.
Impact forces can be reduced by using deformable edges.
Warning!! While the autoset function is running, the obstacle detection
function is not active. Consequently, the installer must monitor the
automated system's movements and keep people and property out
of range of the automated system.
INSTALLATION TEST PROCEDURE
1. Run the AUTOSET cycle (*)
2. Check the impact forces: if they fall within the limits (**) skip to point 10 of the
procedure, otherwise
3. Where necessary, adjust the speed and sensitivity (force) parameters: see
parameters table.
4. Check the impact forces again: if they fall within the limits (**) skip to point 10
of the procedure, otherwise
5. Apply a shock absorber profile
6. Check the impact forces again: if they fall within the limits (**) skip to point 10
of the procedure, otherwise
7. Apply pressure-sensitive or electro-sensitive protective devices (such as a
safety edge)
8. Check the impact forces again: if they fall within the limits (**) skip to point 10
of the procedure, otherwise
9. Allow the drive to move only in "Deadman" mode
10. Make sure all devices designed to detect obstacles within the system's operating
range are working properly
(*) Before running the autoset function, make sure you have performed all the
assembly and make-safe operations correctly, as set out in the installation
warnings in the drive's manual.
(**) Based on the risk analysis, you may find it necessary to apply sensitive
protective devices anyway
13.8) STATISTICS MENU (STAT)
Used to view the version of the board, the total number of operations (in
hundreds), the number of transmitters memorized and the last 30 errors (the
first 2 digits indicate the position, the last 2 give the error code). Error 01 is the
22 -
ARES ULTRA BT A 1500 - 1500 V UL
www.BFTGateOpeners.com | (800) 878-7829 | Sales@BFTGateOpeners.com
INSTALLATION MANUAL
Safety input configuration SAFE2
Safety input configuration SAFE1
most recent.
13.9) PASSWORD MENU (PASSWORD)
Used to set a password for the board's wireless programming via the U-link network.
With "PROTECTION LEVEL" logic set to 1,2,3,4, the password is required to access
the programming menus. After 10 consecutive failed attempts to log in, you will
need to wait 3 minutes before trying again. During this time, whenever an attempt
is made to log in, the display will read "BLOC". The default password is 1234.
14) CONNECTION WITH EXPANSION BOARDS AND UNIVERSAL HANDHELD
PROGRAMMER VERSION> V1.40 (Fig. O) Refer to specific manual.
WARNING! Incorrect settings can result in damage to property and injury to people
and animals.
15) U-LINK OPTIONAL MODULES
Refer to the U-link instructions for the modules.
15.1) REFER TO THE U-LINK MODULE'S INSTRUCTIONS (FIG. P).
Refer to the U-link instructions for the modules.
NOTE: On the board set as the Slave, the Safety Edge input (Safety Edge/ Test
Safety Edge/ 8k2 Safety Edge) should only be set to SAFE2.
16) REVERSING THE OPENING DIRECTION (Fig.Q)
17) RESTORING FACTORY SETTINGS (Fig.R)
WARNING: this operation will restore the control unit's factory settings and all
transmitters stored in its memory will be deleted.
WARNING! Incorrect settings can result in damage to property and injury to
people and animals.
- Cut off power to the board (Fig.R ref.1)
- Open the Stop input and press the - and OK keys together (Fig.R ref.2)
- Switch on the board's power (Fig.R ref.3)
- The display will read RST; confirm within 3 sec. by pressing the OK key (Fig.R ref.4)
- Wait for the procedure to finish (Fig.R ref.5)
- Procedure finished (Fig.R ref.6)