Frequency conversion board fault table:
Protection/fault
Drv1 MOP alarm
Inverter offline
IPM protection
Comp. Driver Failure
DC Fan Fault
IPM Overcurrent
Inv. DC Overvoltage
Inv. DC less voltage
Inv. Input less voltage
Inv. Input Overvolt.
Inv. Sampling Volt.
Comm. Err DSP-PFC
Input Over Cur.
PFC fault
IPM Overheating
Weak Magnetic Warm
Inv. Input Out Phase
IMP Sampling Cur.
Inv. Temp. Probe Fail
Inverter Overheating
Inv. Overheating Warm
Comp. Over Cur. Warm
Input Over Cur. Warm
EEPROM Error Warm
V15V
over/undervoltage fault
Fault
Reason
display
F01
MOP drive alarm
Frequency conversion board and
F02
mainboard communication failure
F03
IPM modular protection
Lack of phase, step or drive
F04
hardware damage
Motor current feedback open circuit
F05
or short circuit
F06
IPM Input current is large
DC bus voltage > Dc bus over-
F07
voltage protection value
DC bus voltage < Dc bus over-
F08
voltage protection value
The input voltage is low, causing the
F09
input current is high
The input voltage is too high, more
F10
than outage protection current RMS
F11
The input voltage sampling fault
F12
DSP and PFC connect fault
F26
The equipment load is too large
F27
The PFC circuit protection
F15
The IPM module is overheat
Compressor magnetic force is not
F16
enough
F17
The input voltage lost phase
F18
IPM sampling electricity is fault
The temp. sensor is broken or short
F19
circuit
F20
The transducer is overheat
F22
Transducer temperature is too high
F23
Compressor electricity is large
F24
Input current is too large
F25
MCU error
F28
The V15V is overload or undervoltage
Elimination methods
Recovery after the 150s
Check the communication connection
Recovery after the 150s
Check the measuring voltage, check
frequency conversion board hardware
Check whether current return wires
connected motor
Check and adjust the current
measurement
Check the input voltage measurement
Check the input voltage measurement
Check the input voltage measurement
Check the input voltage measurement
Check and adjust the current
measurement
Check the communication connection
Check whether the unit is overloaded
Check the PFC switch tube short circuit or
not
Check and adjust the current
measurement
Restart the unit after multiple power
failures, if the fault still exists, replace the
compressor
Check and measure the voltage
adjustment
Check and adjust the current
measurement
Check or change the temp. sensor
Check and adjust the current
measurement
The compressor over-current protection
Check and adjust the current
measurement
Check and adjust the current
measurement
Check whether the chip is damaged,
replace the chip
Check the V15V Input voltage in range
13.5v-16.5v or not
35