Terminal AI3 / AI3: Analogue Input Capacity Control
• Be sure not input more than DC10 V in analogue input terminal.
• To ease the integration of the DX COIL with the DDC the capacity control is able to operate with a STEPPED or
LINEAR function from the analogue input.
• To select either a STEPPED (default) or LINEAR response, from the analogue input, use SW501 Bit4.
• Terminal AI4 / AI4 cannot be used.
SW501 Bit4
OFF
STEP response to analogue input
ON
LINEAR response to analogue input
TCB-IFDMR01UP-UL
Shield wire MAX. 656'12" (200 mm)
AI3
Input
0 - 10 V
AI3
Cooling Mode
Capacity control STEP
SW501
Bit4
ON
OFF
(Linear)
(Stepped)
ΔT = TA (°F) - Set temp. (°F)
10.00
10.00
(Max demand, Approx. ΔT = +4°F (+2°C)
9.50
8.20
9.00
7.45
8.50
6.70
(Approx. ΔT = +2°F (+1°C)
8.00
5.95
7.00
5.20
6.00
4.45
5.00
3.70
(Keep the current temperature, ΔT = 0°F)
4.00
2.95
3.00
2.20
2.00
1.45
(Min demand, Approx. ΔT = -2°F (-1°C)
1.50
0.70
STEP 0 (No operation)
0.00
0.00
Terminal
Locally procured
0 - 10 V Signal (+)
GND (-)
(V)
STEP 11
(Stepped)
(Linear)
8.00
9.30
STEP 10
7.25
8.80
STEP 9
6.50
8.30
STEP 8
5.75
7.80
STEP 7
5.00
6.80
STEP 6
4.25
5.80
STEP 5
3.50
4.80
STEP 4
2.75
3.80
STEP 3
2.00
2.80
STEP 2
1.25
1.80
STEP 1
0.50
1.30
SW501
Bit4
ON
OFF
Capacity control STEP
(Linear)
(Stepped)
ΔT = Set temp. (°F) - TA (°F)
10.00
10.00
(Max demand, Approx. ΔT = +4°F (+2°C)
9.00
9.70
8.00
8.95
7.00
8.20
6.00
7.45
5.00
6.70
(Approx. ΔT = +2°F (+1°C)
5.95
4.50
4.00
5.20
3.50
4.45
3.00
3.70
(Keep the current temperature, ΔT = 0°F)
2.50
2.95
2.00
2.20
1.50
1.45
(Min demand, Approx. ΔT = -2°F (-1°C)
1.00
0.70
STEP 0 (No operation)
0.00
0.00
– 30 –
Heating Mode
(V)
STEP 13
(Stepped)
9.50
STEP 12
8.75
STEP 11
8.00
STEP 10
7.25
STEP 9
6.50
STEP 8
5.75
STEP 7
5.00
STEP 6
4.25
STEP 5
3.50
STEP 4
2.75
STEP 3
2.00
STEP 2
1.25
STEP 1
0.50
(Linear)
8.80
7.80
6.80
5.80
4.80
4.30
3.80
3.30
2.80
2.30
1.80
1.30
0.80