CONFIGURATION
To configure the device accordingly with your application needs, refer to the below instructions.
Press and hold the ON/OFF
key for at least 3 seconds
"Edi" is
displayed
Release the
ON/OFF key
"Pn"
(no. of
[+] key
parameter) is
[-] key
displayed
ON/OFF
The value of
[+] key
the selected
parameter is
[-] key
displayed
ON/OFF
Store the set value and increase
the parameter number.
At last parameter, exit the
configuration mode.
Meaning of Parameters
P1:
This parameter allows to select the measurement type, pH or redox (mV).
P2:
This parameter allows to configure the working mode of level contact:
0 = NO (normally open, standard configuration)
1 = NC (normally closed, fail-safe mode)
P3:
This parameter allows to store the status of the ON/OFF button at the system shutdown:
0 = at start-up the pump is always enabled
1 = at start-up the pump restores its status at shutdown
P4:
This parameter allows to set the pump working mode:
0 = OFF
to monitor the measurement without intervening, for example during the plant start-up
1 = ON
to manually force the dosage, for example during the plant start-up or maintenance
EF117_r1.0 – 05/2018
Increase /
decrease the
parameter
number
Increase /
decrease the
parameter
value
the pump is always off, independently from measured value: this option allows
the pump is always on, independently from measured value: this option is used
Parameter
Description
Measure type
0 = pH with two decimal
P1
1 = pH with one decimal
2 = Redox
Level input:
P2
0 = NO
1 = NC
Storage of the ON/OFF
key status at shutdown
P3
0 = no
1 = yes
Control type
0 = OFF
1 = ON
2 = ON/OFF acid
P4
3 = Proportional acid
4 = ON/OFF chlorine
5 = Proportional
chlorine
Working threshold
P5
0 to 999 (mV)
Hysteresis
P6
0 to 200 (mV)
Delay at start-up
P7
0 to 30 minutes
Alarm delay
P8
0 to 600 minutes
Default
Set
value
value
2
0
1
4
650
20
0
0