30" DUAL FUEL SLIDE-IN RANGE INSTALLATION INSTRUCTIONS
(Models with an Electric Oven and a Gas Cooktop)
4 | Gas Supply -— Installation
When shipped from the factory, this unit is designed to
operate on 4"°(10,16cm) water column (1.0 kPa) Natural
gas manifold pressure. A convertible pressure regulator is
connected to the range manifold and MUST be connected
in series with the gas supply line. To access the regulator,
remove the drawer.
For proper operation, the maximum
inlet pressure to
the regulator should be no more than 14"(35,56cm) of
water column pressure (3.5 kPa).
The inlet pressure to the regulator must be at least 1" (.25
kPa) greater than the regulator manifold pressure setting.
The regulator is set for 4"(10,16 cm) water column (1.0
kPa) Natural gas manifold pressure; the inlet pressure
must be at least 5"(42.60 cm) water column (1.25 kPa)
Natural gas. For LP/Propane gas, the regulator must be
.
set for 10"(25,4 cm) water column (2.5 kPa) manifold
Connection
to Pressure Regulator
pressure; the inlet pressure must be at least 11"(27,9 cm) __ he regulator is already installed on the appliance.
water column (2.75 kPa).
NNO
Do not make the connection too tight.
The supply line should be equipped with an approved
The regulator is die cast. Overtightening may crack the
shutoff valve (see Figure 11). This valve should be located — regulator resulting in a gas leak and possible fire or
in the same room as the range and should be in alocation
—_ explosion.
that allows ease of opening and closing. Do not block
access to the shutoff valve. The valve is for turning on
or shutting off gas to the appliance. Open the shutoff
valve in the gas supply line. Wait a few minutes for gas to
move through the gas line.
fi
Figure 8
The gas supply between
the shutoff valve and the
regulator may be connected by rigid piping or by A.G.A./
C.G.A. - approved flexible metallic union-connected
piping where local codes permit use.
The gas supply piping can be through the back wall
(Figure 8, zone 1) or through the floor (Figure 8,
zone 2):
PRESSURE REGULATOR LOCATION
Zone 1 - Through the Back Wall (7"_X 6") - The best
Figure 9
place to have your gas line in is between 1" (2.5 cm) and
8" (20.3cm) from the floor and within 3" (7.6 cm) from
the center line.
Zone 2 - Through the Floor (~2" X 24") - The gas line
ene
are
Gases"
Flare
Pressure
ny
\
utoff
'
:
Regulator
can also come through the floor within 12"
(30.5 cm)
Valve
Union
Union
}
from the center line against the back wall.
6
le
S
Access
Cap
Flexible
Connector
All connections must be wrench-tightened
Figure 10