HCS-D User Manual
WIRING INSTRUCTIONS (Hardwired HCS-D)
Route the HCS-D conduit to a nearby junction box. Use the
included ½" trade size watertight conduit fitting and sealing washer
to provide a moisture-resistant seal between the conduit fitting
and the junction box. If necessary, drill a 7/8" diameter hole to
accommodate the conduit fitting. For outdoor installations, ensure
the junction box is fully sealed using appropriate electrical grade
silicone sealant.
Figure 10: Wiring the
HCS-D in a Junction
Box
Before connecting the HCS-D service
conductors, please carefully read the
section of this manual titled Installation -
Service Connections. If unsure of the type
of power provided at the service panel,
please consult with the local utility or
call a Service Representative for
assistance.
NOTE: The three supplied HCS-D40 and
HCS-D50 service conductors use stranded
8 AWG, 90ºC copper wire.
The insulation of each conductor is color
coded for standard 240V AC installation:
Green:
Ground
Black:
Line 1 (120V AC to Ground)
Red:
Line 2 (120V AC to Ground)
24