A1
M:XXXXX,XXXXX
R
WWWWW,WWWWW Alarm triggered threshold high value
Example:
A1M:0.600,1.000,1,0.500,0,0.100
0.600
1.000
1
0.500
0.100
Standard range of data captured in A/D channel 1 is 4 ~ 20mA.
A1 reported value will be: range x (0.012 x 250 – start value) / (5 – start value).
When current input is 12mA, A1 = 0.6 x (0.012 x 250 – 1) / (5 – 1).
When A1 value is over 0.500 or below 0.100, alarm will be triggered and SMS alarm message will be sent.
A1 value is reported by command 2 [PWD:XXXX,STATUS%]
A
X
BBBB
CCC
A2M
• Manual Health Report
Command: PWD:XXXX,STATUS%
[SMS message received]
ST:XXX;T:2005/01/28/13:00;V:XXXX;A1:0000;A2:0000;K1:X;K2:X;K3:X;K4:X;K5:X;K6:X;K7:X;K8:X;OUT1:Y;O
UT2:Y;OUT3:Y;#
• A/D Parameters Setup
Command: PWD:XXXX,ADVALE2:XXXXX,NNNNN,Y,ZZZZZ,WWWWW%
2
XXXXX
NNNNN
Y
ZZZZZ
WWWWW
CU2200_v4
A/D channel 1
Range value, start value
A/D value triggered alarm enabled
Alarm triggered threshold low value
Range from 0 to 600
Start value is 1.000 (4mA x 250 = 1)
Alarm enabled
Threshold high
Threshold low
Alarm report to control centre 1
Alarm report to control centre 2
Report status for 4 phone numbers
0 means no alarm report
1 means SMS only
2 means phone dial only
3 means SMS first, then phone dial
Relay output control
0 means no relay output control
1 means relay output triggered by alarm
A/D channel 2
A/D channel 2
Measuring range
Start value
1: triggered alarm enabled
0: triggered alarm disabled
Threshold high
Threshold low
0 means no report
1 means report
0 means no report
1 means report