Descargar Imprimir esta página

Honeywell BK-G40 Manual De Instrucciones página 13

Contadores industriales de gas de membranas

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 149
2. Intended use and field of application
This product is intended to be used for the calibratable volumetric metering
of:
 flammable gases: natural gas/town gas/propane/butane
 non-flammable gases: air/nitrogen/inert gases
 inert gases pursuant to DVGW Code of Practice G260
This product is not intended:
 for metering aggressive gases, e.g. biogas or sewage gases, oxygen,
acetylene.
The permitted operating/ambient temperature and gas temperature can be
found on the type label/index plate. If operated within the gas temperature
range, the measurement error still lies within the required error limits. If no
gas temperature t
For meters on which conformity with Directive 2014/32/EU (MID) or
Regulation SI 2016/1153 (UK) is declared on the main plate, the following
specifications also apply:
The meters are suitable for mechanical environments of Class M1 of the
Directive. For meters with an encoder index, Class E2 for electromagnetic
environments also applies.
Conformity with Directive 2014/32/EU (MID) or Regulation SI 2016/1153
(UK) is declared by affixing the following markings:
C M.. 0102
on which the 2-digit year of the declaration of conformity (year of
construction) is to be inserted after the letter "M".
Elster's industrial diaphragm gas meters are always to be transported and
stored in the upright position.
The permitted storage temperature is -25°C to +60°C.
73020212j
© Elster GmbH | All rights reserved. Subject to modification
is specified on the index plate, t
g
Honeywell
= t
applies.
g
m
M.. 0086
B
13

Publicidad

loading

Este manual también es adecuado para:

Bk-g65Bk-g100