Para ampliar información sobre las conexiones RS-485 consultar el manual de accesorios de comunicación vía RS-485.
EN
For more information on RS-485 connections, see the RS-485 communication accessories manual.
ES
Parámetros del transformador de intensidad para instalaciones trifásicas con transformadores de corriente
(vatímetro A65+)
Para realizar una correcta selección del transformador de intensidad será necesario contemplar los parámetros que se indican a
continuación:
Ip: Corriente nominal del primario (A)
La corriente nominal en el primario debe ser superior o igual a la corriente máxima por fase del sistema.
Is: Corriente nominal del secundario (A)
Valor de corriente nominal en el secundario del transformador de intensidad.
La corriente nominal del vatímetro que se va a conectar al secundario del transformador es In = 5 A y la corriente máxima del
mismo es Imax = 10 A.
Para asegurar la precisión de medida del vatímetro será necesario emplear al menos un transformador de intensidad cuya
corriente nominal secundaria sea Is = 5 A.
Para transformadores cuya corriente nominal secundaria Is sea inferior a 5 A, Ingeteam no asegura la precisión
y correcto funcionamiento del sistema de autoconsumo instantáneo instalado.
No se podrá emplear un transformador cuya corriente nominal secundaria sea superior a la corriente máxima del vatímetro, es
decir, 10 A.
K
: Relación de transformación (A)
N
Relación entre la corriente nominal del primario y la corriente nominal del secundario.
Se expresa en forma de fracción. Ejemplo: K
= (150 A / 5 A)
N
Cl: Clase de precisión
La clase de precisión es el límite del error de corriente porcentual cuando se trabaja a corriente nominal.
Ingeteam exige que la clase de precisión de los transformadores de intensidad sea 0,5 (Cl 0,5).
Se admiten también aquellos transformadores de intensidad cuya clase de precisión permita realizar la medida de corriente con
un error inferior al que establece la clase de precisión 0,5.
Sn: Potencia de precisión ( VA )
Este parámetro describe la capacidad del transformador para hacer circular la corriente por el secundario a través de una carga
manteniendo la clase de precisión. Será necesario calcular la potencia consumida en VA en el secundario del transformador de
intensidad (considerar en este cálculo la suma del cableado y el vatímetro A65+).
Se recomienda elegir la potencia normalizada más cercana posible a la calculada. La potencia normalizada siempre será superior
a la calculada.
Para el correcto funcionamiento se debe cumplir con la siguiente relación:
Sn ≥ Sc + Sw
(Ver nota de aplicación)
En caso de no cumplirse con esta relación Ingeteam no asegura la precisión y correcto funcionamiento del sistema de
autoconsumo instantáneo que se instale.
Nivel aislamiento
Se deberá emplear transformadores de intensidad que aporten un nivel de aislamiento ≥ 1 kV.
Considerar en los parámetros que definen las características de un transformador de intensidad las condiciones
ambientales de funcionamiento de la instalación.
El circuito secundario de un transformador de intensidad en servicio nunca debe quedar en circuito abierto.
Nota de aplicación
Sw: Potencia consumida en el vatímetro A65+ expresada en VA. La potencia disipada por el vatímetro para una corriente nominal
In = 5 A es Sw = 0,3 VA por fase.
Para corrientes diferentes a 5 A, la potencia consumida por el vatímetro asociada a la medida se puede obtener como:
Sw = I
x Zw, donde Zw = 0,3 VA / (5 A)
= 12 mΩ
2
2
Sc: Potencia consumida por el cableado en el secundario del transformador de intensidad en VA. Se puede calcular como:
Sc = I
2
x Zc
La impedancia del cable se considerará a una temperatura ambiente de al menos 40 ºC.
Ip
Ip
Sn
Is
Is
A65+
Sc
Sw
Sn ≥ Sc + Sw
F2
EN
Current transformer parameters for three-phase installations with current transformers (A65+ Wattmeter)
The parameters indicated below must be considered in order to select the correct current transformer:
Ip: Nominal primary current (A)
The nominal current on the primary must be greater than or equal to the maximum current per system phase.
Is: Nominal secondary current (A)
Nominal current value on the current transformer secondary.
The nominal current of the Wattmeter to be connected to the transformer secondary is In = 5 A and its maximum current is Imax = 10 A.
To ensure the Wattmeter measures precisely, at least one current transformer with a nominal secondary current of Is = 5 A must be used.
Ingeteam does not guarantee the precision and correct functioning of the installed self-consumption system when transformers
with a nominal secondary current (Is) of less than 5 A are used.
Transformers with a nominal secondary current that is higher than the maximum current of the Wattmeter (i.e. 10 A) may not be used.
K
: Transformation ratio (A)
N
Ratio between the nominal current of the primary and the nominal current of the secondary.
This is expressed as a fraction. Example: K
= (150 A / 5 A)
N
Cl: Precision class
The precision class is the percentage current error limit when operating at nominal current.
Ingeteam requires a current transformer precision class of 0.5 (Cl 0.5).
Current transformers with a precision class that allows for current measurement with an error below that established by precision class 0.5 are
also accepted.
Sn: Precision power ( VA )
This parameter describes the capacity of the transformer to make the current run around the secondary through a load, maintaining the
precision class. The power consumed in the current transformer secondary must be calculated in VA (bear in mind the sum of wiring and the
A65+Wattmeter in this calculation).
The standardised power closest to that calculated should be selected. The standardised power must be higher than that calculated.
The following ratio must be met for correct operations:
Sn ≥ Sc + Sw
(See application note)
Ingeteam does not guarantee the precision and correct functioning of the installed self-consumption system if this ratio is not met.
Isolation level
Current transformers providing an isolation level of ≥ 1 kV must be used.
Bear the environmental operating conditions of the installation in mind in the parameters defining the features of a current
transformer.
The secondary circuit of an operational current transformer must never remain open-circuited.
Application note
Sw: Power consumed in the A65+ Wattmeter expressed in VA. The power dissipated by the Wattmeter for a nominal current In = 5 A is Sw = 0.3
VA per phase.
For currents other than 5 A, the power consumed by the Wattmeter associated to the measurement can be obtained as:
Sw = I
x Zw, where Zw = 0.3 VA / (5 A)
2
Sc: Power consumed by the wiring in the current transformer secondary in VA. This can be calculated as:
Sc = I
2
x Zc
The cable impedance is considered at an ambient temperature of less than 40 ºC.
Config
ES
Configuración del INGECON SUN 3Play
Tras la instalación y conexión del vatímetro habrá que configurar el inversor INGECON SUN 3Play para su correcto funcionamiento.
Para realizar esta configuración el inversor debe estar alimentado.
Para la configuración del autoconsumo se debe introducir previamente la contraseña de instalador (3725) dentro de Menú principal >
L1
Ajustes avanzados.
L2
Acceder al menú Menú principal > Ajustes > Autoconsumo > Modo para seleccionar el modo de autoconsumo. Elegir Auto-limitado
L3
CG EM24
.
(2)
También habrá que configurar el balance de potencia que se desea en la instalación. Existen tres opciones:
•
Balance positivo: el inversor determinará que, siempre que las cargas sean suficientes, exista un consumo de la magnitud
fijada.
•
Balance 0.
•
Balance negativo: el inversor determinará que, siempre que la potencia generada por el campo fotovoltaico sea suficiente,
exista una inyección de potencia de la magnitud fijada.
Para configurar el balance acceder a Menú principal > Ajustes > Autoconsumo > Consigna de potencia. Seleccionar la potencia
deseada mediante las teclas
Si el autoconsumo instantáneo se ha configurado correctamente aparecerá el símbolo
inversor en la pantalla principal. En el caso de que este símbolo no aparezca se deberá volver a configurar correctamente.
Si dicho símbolo apareciese parpadeando significa que existe un fallo de comunicación del cable RS-485. Revisar las conexiones y
conectar correctamente hasta que desaparezca el fallo.
Si el país seleccionado en el inversor dentro del menú Menú principal > Ajustes avanzados > País normativa es España, la opción
(1)
de Autoconsumo vendrá configurada de serie y no será posible modificarla, cumpliendo de este modo la normativa propia del país.
Para el resto de países sí será posible modificar esta configuración.
(2)
Una vez seleccionado el modo Auto-limitado CG EM24 de Autoconsumo no será posible activar el modo MPPT. En caso de querer
activar el modo MPPT contactar con el SAT de Ingeteam.
EN
Configuring the INGECON SUN 3Play
After installing and connecting the Wattmeter it is necessary to set up the INGECON SUN 3Play inverter for it to operate correctly. The
inverter must be powered to carry out this configuration.
In order to configure the unit, an installer password (3725) must be introduced in Main menu > Advanced settings.
Access the Main menu > Settings > Self-consumption > Mode to select the self-consumption mode. Select Self-limiting CG EM24
It is also necessary to configure the power balance that you require in the installation. There are three options:
•
Positive Balance: the inverter will establish, provided that the loads are sufficient, that the consumption is at the set value.
•
Balance 0.
•
Negative Balance: the inverter will establish, provided that the power generated by the photovoltaic array is sufficient, that
there is an injection of power to match the set value.
To configure the balance access the Main menu > Settings > Self-consumption > Power setpoint. Select the desired power using the
keys
or
If the instantaneous self-consumption has been correctly configured the
the main screen. In the event that this symbol does not appear it is necessary to re-configure the balance.
If the symbol appears flashing, this means that there is a communication failure in cable RS-485. Check the connections and connect
the cable correctly until the fault disappears.
(1)
If the country selected in the inverter under the Main menu > Advanced settings > Country regulations is Spain, the
Self-consumption option will come factory configured and it will not be possible to modify it, thus complying with the country's
legislation. For the remaining countries it will be possible to modify this configuration.
(2)
Once you have selected Self-limiting CG EM24 mode in Self-consumption it will not be possible to enable MPPT mode. If you want
to enable MPPT mode, contact the Ingeteam Technical Service.
= 12 mΩ
2
(1)
o
. Pulsar OK para confirmar.
W
luciendo de forma continua junto al
(1)
. Press OK to confirm.
W
symbol appears continuously together with the inverter on
(2)
.